Equipment Phase Instructions (PSC, PCMD, POVR, PFL, PCLF, PXRQ, PRNP, PPD, PATT, PDET)

Example:

Relay Ladder

Structured Text

If ThisPhase.StepIndex.1 = 1 (The routine is at step 1.), then

Send the Acquire Resources request to FactoryTalk Batch software. The DataValues tag is a DINT array that contains the
equipment IDs of the resources.

When RQ_Control[0].PC = 1 or RQ_Control[0].ER = 1 (The request is complete or it failed.), then

Done = 1. (This signals the sequence to go to the next step.)

This action executes one time to initialize the data values of the
PXRQ instruction to the equipment IDs of the resources it will
acquire.

If Step_000.FS = 1 (first scan of the step)

Or RQ_Control[0]. PC = 0 (The PXRQ instruction is in process.), then

Send the Acquire Resources request to FactoryTalk Batch software. The
DataValues tag is a DINT array that contains the equipment IDs of the
resources.

If RQ_Control[0]. PC = 1 (The request is complete.), then

Go to the next step.