Execution guidelines – Rockwell Automation 1794-Lxxxx PhaseManager User Manual

Page 34

Advertising
background image

34

Publication LOGIX-UM001B-EN-P - April 2010

Chapter 3

Guidelines

Execution Guidelines

A state model makes it much easier to separate the normal execution of your
equipment from any exceptions (faults, failures, off-normal conditions).

Holding

Idle

Running

Held

Restarting

Stopping

Aborting

Stopped

Aborted

Resetting

Complete

Use the resetting, running, and stopping states

for the normal execution of the equipment.

Use the holding, restarting, and aborting states to

handle exceptions (faults, failures, off-normal

conditions).

Guideline

Details

Use the prestate routine to watch for
faults

Use the prestate routine for conditions that you want to watch all the time such as fault bits.
The prestate routine:

• runs all the time.
• runs before each scan of a state.
• runs even in the waiting states (idle, held, complete, stopped, or aborted).

current state

routine

prestate routine

Advertising