PATT Result Codes

If you assign a tag to store the result of a PATT instruction, the instruction
returns one of the following codes when it executes.

Arithmetic Status Flags:

not affected

Fault Conditions:

none

Execution:

Code (Dec)

Description

0

The command was successful.

24579

RSLogix 5000 software already owns the equipment phase.

• This program now also owns the equipment phase.
• Because RSLogix5000 software is higher priority than a program, the

program cannot command the equipment phase.

24582

The program already owns the equipment phase.

24593

One of the following already owns the equipment phase.

• external sequencer (FactoryTalk Batch software)
• another program in the controller

24594

Equipment phase is inhibited, unscheduled, or in a task that is inhibited.

Condition

Relay Ladder Action

Structured Text Action

prescan

The rung-condition-out is set to false.

No action taken.

rung-condition-in is false

The rung-condition-out is set to false.

N/A

rung-condition-in is true

• The instruction executes.
• The rung-condition-out is set to true.

N/A

scan of structured text

N/A

In structured text, instructions execute each time
they are scanned. To limit the scan of an instruction,
use a qualifier of an SFC action and/or a structured
text construct.

instruction execution

The instruction tries to take ownership of the
specified equipment phase.

The instruction tries to take ownership of the
specified equipment phase.

postscan

The rung-condition-out is set to false.

No action taken.