Connect the power supply, Connect the, Power supply – Rockwell Automation Logix5000 Control Systems: Connect PanelView Plus Terminals over EtherNet/IP Quick Start User Manual
Page 15
Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012
15
Prepare the PanelView Plus Terminal Hardware Chapter 1
Connect the Power Supply
This quick start uses a PanelView Plus 1000 terminal with built-in Ethernet port and a
PanelView Plus Logic module, catalog number 2711P-RP1, Series G. The 2711P-RP1 Logic
module uses a 2-position terminal block for power connections.
Complete these steps to connect power to the PanelView Plus terminal.
1.
Install the 2711P-RSACDIN DC power supply for the PanelView Plus terminal on a
DIN rail.
Do not turn on power to the power supply.
For detailed information on how to install a 2711P-RSACDIN DC power supply, see the
AC Power Supply for PanelView Plus/PanelView Plus CE Terminals Installation
Instructions, publication
WARNING: Verify that all incoming power is turned off before wiring power.
GND
+
–
GND
Earth/Ground to Ground Bus
DC -
DC +
2-position
Terminal Block
PanelView Plus
24 VDC
POWER SUPPLY
2711P-RSACDIN
POWER