Cnc input / output descriptions, Ultra-cut 100 xt – Tweco 100 Ultra-Cut Plasma Cutting System with Automated Gas Control User Manual

Page 128

Advertising
background image

ULTRA-CUT 100 XT

A-4

APPENDIX

Manual 0-5303

CNC Input / Output Descriptions

E-Stop input— Requires closed connection rated for

35ma. @ 20VDC

for unit to operate. Factory installed jumper

between TB1-1&2 must be removing when connecting user supplied E-Stop circuit.

4

Start/Stop input—Switch (momentary or sustained) rating 35ma. @ 20 VDC

Start / Stop circuit configurations. Momentary Start / Stop (Latched) is only available at TB1.

MOMENTARY START / STOP

START / STOP

TB1-6

TB1-5

TB1-4

SUSTAINED START / STOP

START

STOP

TB1-5

TB1-6

Divided Arc Voltage output — Arc Voltage signal is isolated from plasma supply, however (-) is common with

other isolated CNC signals. Max Divided Arc Voltage signal level depends on actual arc voltage times divide ratio

however can not exceed approximately 12 V.

3

Analog Current Control input— Analog Current Control includes analog isolation module, separate isolation

module not usually required however it’s low input is common with the other isolated CNC inputs. Scaling of Analog

Current Control input is 0V = 0A, 10V. = MAX output and is linear in between. However MIN output is 5A. User is

responsible for setting correct analog voltage to maintain at least 5A output. To use Analog Current Control on the

I/O PCB set SW 11 to down position and on the CPU PCB set SW8-2 ON (up).
Hold Start input—Normally open, close to hold start. Circuit rating 10 ma. @ 20VDC. Delays pilot ignition, gas

preflow continues. Used by some height controls to flow gas while finding height. Also used for synchronizing starts

when multiple plasma supplies are used on same cutting table. User supplies circuit to keep Hold Start inputs ac-

tive until all torches have found height. Used with CNC START. Apply START to begin gas flow. Same time apply

HOLD to delay ignition until height is found. Remove HOLD to ignite pilot, initiate arc transfer.
Preflow On input— Normally open, close to start preflow prior to normal START signal. Circuit rating 10 ma. @

20VDC. Torch Height Controls (THC) normally issue START signal to plasma supply after torch height has been

found. Then the plasma takes 1-2 seconds (or more) to perform preflow before igniting pilot. Some THCs have

an output that can start preflow early during height finding saving 1-2 seconds on each cut. PREFLOW ON should

remain active for at least 1 second after CNC START is applied. It is OK if it remains on until the end of the cut.

Need to recycle it to begin a new preflow prior to applying START for the next cut.
Pilot On output – Relay contacts rated 1A @ 120 VAC / 28 VDC. Contacts close when pilot on. Can be wired

parallel with Ok to Move contacts to start machine motion when pilot established. Used when starting over holes.

Starting over holes requires setting SW8-1 ON (up) on the CPU PCB for extended pilot time. Using extended pilot

time to start over holes or for cutting over holes will reduce parts life.
OK to Move output — Active when cutting arc is established, arc is transferred. Used to signal cutting table to

start X-Y motion. Relay contacts rated 1A @ 120 VAC or 28 VDC when SW6 set for contacts. When SW6 is

set for DCV, output supplies 15-18 VDC @ 100 ma. May be wired parallel with Pilot On to start cutting machine

motion as soon as pilot established.