Ultra-cut 100 xt, Mc3a mc3b m1 – Tweco 100 Ultra-Cut Plasma Cutting System with Automated Gas Control User Manual

Page 200

Advertising
background image

ULTRA-CUT 100 XT

A-76

APPENDIX

Manual 0-5303

d. If jumping TP3 to TP1 does not turn the fans on then the Relay board or the 40 pin ribbon cable pin 13 is at fault.

Art # 12313

MC3A

MC3B

M1

Torch Coolant Pump

1

2

3

J16

1

2

3

4

J13

(65B)

(66)

(67)

(64B)

CHASSIS GND

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

J8

1

5

3

2

4

Coolant Pump Control

K5

MC3

Coolant pump Control

(163)

(162)

SA4

ARC_SUPPRESSOR

D27

24 VAC

Relay PCB

TP1

TP3

CCM I/O PCB

To test Pump relay jump TP3 to TP1.

+24

J4-13

230 VAC from T1

Coolant flows but flow is less than the required minimum:

Test and adjust the pump/bypass valve:

This test measures the “dead head” or blocked flow pressure at the rear panel coolant supply fitting. Perform

this test only after the coolant system is fully primed, that is after the coolant is circulated throughout the system

and is mostly free of bubbles. It requires a pressure gauge with #� JIC fitting.

The gauge needs to be able to read at least 173 PSI. Remove the coolant supply hose and connect the pressure

gauge in its place. For the Auto-Cut 200 XT connect the gauge in place of the torch coolant supply hose on the

torch connection bulkhead. This is a #5 JIC fitting.

NOTE:

Do not put the gauge in�line and attempt to pinch off the hose to block the flow. It is very difficult to totally block
the flow and failure to do so will result in incorrect setting of the bypass.

Turn the on the unit. You will have � minutes to perform the test/adjustment before the system times out with

a coolant flow fault. If that happens recycling the power gives you another � minutes.

1. The pressure on the gauge should be close to 173 (170-175) PSI. If it is the pump and the bypass are OK.

2. If the pressure is less than 173 PSI adjust the bypass screw clockwise to raise the pressure. If you can

change the pressure with the bypass screw but cannot reach 173 PSI it is likely the pump is worn out or

damaged. If the pressure does not change using the bypass screw it is likely the bypass is defective.

3. If the pressure is above 173 reduce the pressure by adjusting the bypass valve screw counter clockwise.

Coolant flow test:

In addition to the pressure test or in place of it if you don’t have a gauge, determine if the flow returning from

the torch (the flow that passes through the FS1), is greater than the required minimum. With the unit switched

off remove the return hose from the back of the power supply. Place it in a container of a known volume. Turn

the unit on and let the pump run exactly 30 seconds. It should pump at least 3/� gal. (1.� l). Use a larger con-

tainer in case the flow is greater and it overflows.

If the flow is lower than 0.75 GPM:

• Look for restrictions such as sharp bends or something pinching the coolant hoses or torch leads.
• Other possibilities are the bypass valve has been adjusted wrong (someone may have turned the adjust-

ment screw) see pressure test/adjustment above

• The pump is worn out (may be the case with an older unit).

Advertising