Ultra-cut 100 xt – Tweco 100 Ultra-Cut Plasma Cutting System with Automated Gas Control User Manual

Page 32

Advertising
background image

ULTRA-CUT 100 XT

3-�

INSTALLATION

Manual 0-5303

Creating An Earth Ground

1. To create a solid, low resistance, earth ground, drive a 1/2 in (12 mm) or greater diameter copper clad ground

rod at least 6 - 8 ft (1.8 - 2.4 m) into the earth so that the rod contacts moist soil over most of its length. Depend-
ing on location, a greater depth may be required to obtain a low resistance ground (see NOTE). Ground rods,
typically 10 ft (3.0 m) long, may be welded end to end for greater lengths. Locate the rod as close as possible
to the work table. Install a ground wire, 1/0 AWG (European 50 mm2) or greater, between the ground rod and
the star ground point on the cutting table.

NOTE

Ideally, a properly installed ground rod will have a resistance of three ohms or less.

To test for a proper earth ground, refer to the following diagram. Ideally, the reading on the multimeter should be

as shown.

CAUTION

No other connections should be made at the ground rod being tested.

This test assumes the 115 or 230 VAC source neutral is connected to the utility earth ground.

Art # A-07252

WARNING

Use extreme caution. This

test uses live voltage.

NEUTRAL

Earth Grounded

HOT

On 115V AC Line:

3VAC = 3 ohms

1VAC = 1 ohm

On 230V AC Line:

1.5VAC = 3 ohms

0.5VAC = 1 ohm

Ground Rod

with other

connections removed

100W Incandescent

light bulb*

* Can replace light bulb with

a 100w resistor.

Use 100 ohm for 115VAC.

Use 500 ohm for 230VAC

NEUTRAL

PROBE

VAC

HOT

PROBE

Ground Testing

2. Increasing the ground rod length beyond 20 - 30 ft (6.1 – 9.1 m) does not generally increase the effectiveness

of the ground rod. A larger diameter rod which has more surface area may help. Sometimes keeping the soil
around the ground rod moist by continuously running a small amount of water into it will work. Adding salt to the
soil by soaking it in salt water may also reduce its resistance. You may also try a chemical ground rod devise.
When these methods are used, periodic checking of the ground resistance is required to make sure the ground
is still good.

D. Routing Of Torch Leads

1. To minimize RF interference, position torch leads as far as possible from any CNC components, drive motors,

control cables, or primary power lines. If cables have to pass over torch leads, do so at an angle. Do not run
the plasma control or other control cables in parallel with the torch leads in power tracts.

2. Keep torch leads clean. Dirt and metal particles bleed off energy, which causes difficult starting and increased

chance of RF interference.

Advertising