Ultra-cut 100 xt – Tweco 100 Ultra-Cut Plasma Cutting System with Automated Gas Control User Manual

Page 197

Advertising
background image

ULTRA-CUT 100 XT

Manual 0-5303

APPENDIX

A-73

Troubleshooting:

1. First note whether the fault is an “E” meaning it’s currently low or an “L” meaning it was low but isn’t now.

Flow that remains low could indicate a failed component or a blockage such as clogged filter or pinched

hose. It also means you should be able to measure the flow to determine if it is really low or the sensor has

a problem.

2. First recycle power. If flow is still low or a component is defective the code should change to 404. Go to

that section for further troubleshooting.

3. If after recycling power there is no code, continue cutting to see if it occurs again. Take note of when it oc-

curs, for example if it’s with the torch at one end of the table, perhaps the leads get pinched there? In any

case go to code 404 section for more information.

403

Coolant overheated.

TS1 is a linear negative temperature coefficient (NTC) resistor sensor attached to the brass fitting at the exit of

the bypass valve. Here we determine the coolant being supplied to the torch is below the required temperature

which is currently 75 deg C (1�7F). The radiator is on the lower right side of the unit. The fan(s) are behind it

and blow out through the radiator. 100A & 200A units may either have 2 smaller fans or one larger one. The

300 & �00A units have one larger one.

Fans operate during cutting and for � minutes after last cut then shut off. Exception is AC 200 XT where the

fans are on whenever power is on. The external heat exchanger, HE�00, fan is thermostatically controlled so it

only comes on when coolant is over �0 deg C. It will shut off when the other fans shut off.

Possible reasons for coolant overheated:

Coolant fan(s) failed or defective fan control relay MC2.

• Radiator fins clogged with dirt.
• Duty cycle exceeded (ambient temperature above 40 deg C and operating at high duty cycle).
• Operating with an object placed in close proximity to the air outlet (right side of the unit) or the front

panel inlet openings.

• Operating for extended time with right lower side panel removed.
• Defective Relay board.
• Defective CCM.

Troubleshooting:

1. Check for air blowing out of the unit. Remember, except for the AC 200 XT, the fans only run when CNC

START is applied and for 4 minutes after cutting, you may have to apply start again to restart the 4 minute

time. Fans may be forced on by jumping TP2 on the CCM I/O board to TP1 (ground).
a. If using the external HE�00XT heat exchanger, optional for 300A, standard for �00A, check for air blow-

ing out of it. Note that the HE�00XT fan, controlled by a thermal switch in the HE�00XT, only runs if

the coolant is over �0 deg C and the internal fans are operating. With the 100 & 200A if it has 2 fans

make sure both fans are operating by checking for air both top and bottom of the opening. The fans are

difficult to see, perhaps you can use an inspection mirror. Be careful not to get the mirror or your hands

into the blades.

Advertising