About Your System

41

Alert! Node
Interleaving
disabled! Memory
configuration
does not support
Node
Interleaving.

The memory configuration

has changed (for example, a

memory module has failed)

so that node interleaving

cannot be supported. The

system will run but without

node interleaving.

Ensure that the memory

modules are installed in a

configuration that supports

node interleaving. Check

other system messages for

additional information for

possible causes. For memory

configuration information,

see "General Memory

Module Installation

Guidelines" on page 122.

If the problem persists, see

"Troubleshooting System

Memory" on page 157.

Alert! Power
required exceeds
PSU wattage.
Check PSU and
system
configuration.
Alert!
Continuing
system boot
accepts the risk
that system may
power down
without warning.

The system configuration of

processor(s), memory

modules, and expansion

cards may not be supported

by the power supplies.

If any system components

were just upgraded, return

the system to the previous

configuration. If the system

boots without this warning,

then the replaced

component(s) are not

supported with this power

supply. If Energy Smart

power supplies are installed,

replace them with the High

Output power supplies to

use the components. See

"Power Supplies" on page 95.

Alert! Redundant
memory disabled!
Memory
configuration
does not support
redundant
memory.

Redundant memory was

enabled in the System Setup

program, but the current

configuration does not

support redundant memory.

A memory module may be

faulty.

Check the memory modules

for failure. See

"Troubleshooting System

Memory" on page 157. Reset

the memory setting, if

appropriate. See "Using the

System Setup Program and

UEFI Boot Manager" on

page 57.

Table 1-3. System Messages

(continued)

Message

Causes

Corrective Actions