Dell DX6000 User Manual

Page 26

Advertising
background image

26

About Your System

E122E

On-board

regulator

failed. Call

support.

One of the on-board

voltage regulators failed.

Remove AC power to the

system for 10 seconds and

restart the system.
If the problem persists,

see "Getting Help" on

page 189.

E1310

Fan ## RPM

exceeding

range. Check

fan.

RPM of specified fan is

outside of the intended

operating range.

See "Troubleshooting

System Cooling

Problems" on page 161.

E1311

Fan module ##

RPM exceeding

range. Check

fan.

RPM of specified fan in

specified module is outside

of intended operating

range.

See "Troubleshooting

System Cooling

Problems" on page 161.

E1313

Fan

redundancy

lost. Check

fans.

The system is no longer fan

redundant. Another fan

failure would put the

system at risk of over-

heating.

Check LCD for additional

scrolling messages. See

"Troubleshooting a Fan"

on page 162.

E1410

System Fatal

Error

detected.

A fatal system error has

been detected.

Check LCD for additional

scrolling messages.

Remove AC power to the

system for 10 seconds and

restart the system.
If the problem persists,

see "Getting Help" on

page 189.

E1414

CPU # temp

exceeding

range. Check

CPU heatsink.

Specified processor is out of

acceptable temperature

range.

Ensure that the processor

heat sinks are properly

installed. See

"Troubleshooting the

Processor" on page 172

and "Troubleshooting

System Cooling

Problems" on page 161.

Table 1-1. LCD Status Messages

(continued)

Code

Text

Cause

Corrective Actions