Chapter 1

Concord Express Installation Instructions

9

(B) Class 2, Class 3, and power-limited fire alarm circuit conductors must be
installed as Class 1 or higher circuits.

Table 1 below describes panel voltage/current output ranges. See Appendix A for
maximum and standby device current draw.

Table 1: Panel voltage/surrent output ranges

Panel terminal

Voltage range

Max. current

4 (+12V)

8.5 - 14.2 VDC
9.1 - 14.2 VDC (UL)

750 mA—non-UL Listed systems
90 mA—UL Listed systems

7 (OUT1/+12)

8.5 - 14.2 VDC

1.25 A at default configuration—non-UL Listed systems
650 mA—UL Listed systems

17 (Z6/2W+)

8.9 - 13.7 VDC

80 mA

Total system wire allowed varies depending on devices powered by the panel,
wire length between devices and the panel, and the combined wire length of all
devices.

Table 2 below describes the maximum wire length allowed between compatible
devices and the panel.

Table 2: Maximum device wire lengths

Device

Max. wire length to panel

Wire type

AC Power Transformer

18 AWG—25 ft.

Stranded

Earth Ground

16 AWG—25 ft.

Solid

Telephone (RJ-31X)

as required

Stranded

Detection Devices

22 or 18 AWG—300 ohms maximum loop resistance +
2k end-of-line

Stranded

2-Wire Smoke Detectors 22 AWG—330 ft.

18 AWG—830 ft.
(based on 10 ohms maximum loop resistance + 2k
end-of-line)

Stranded

Sirens

22 AWG—80 ft.
18 AWG—200 ft. when using siren models 13-469 or
13-046

Stranded

SuperBus 2000 2x16
LCD Alphanumeric
Touchpad

22 AWG—300 ft.
18 AWG— 750 ft.

Stranded

SuperBus 2000 Fixed
Display LCD Touchpad

22 AWG—300 ft.
18 AWG— 750 ft.

Stranded

SuperBus 2000 2x20
LCD Alphanumeric
Touchpad

22 AWG—250 ft.
18 AWG— 600 ft.

Stranded