Appendix A

86

Concord Express Installation Instructions

Part
no.

Descritpion

Q

u

a

n

ti

ty

Standby current
draw

Standb
y
current
subtota
l

Maximum
current draw

Maximum
current
subtotal

SuperBus 2000 Devices (4 maximum)

60-
746-01

SuperBus 2000
2x16 LCD
Alphanumeric
Touchpad

57 mA

90 mA

60-820 SuperBus 2000

Fixed Display
Touchpad

33 mA

65 mA

60-
803-04

SuperBus 2000
2x20 LCD
Alphanumeric
Touchpad

75 mA

120 mA

60-
804-04

SuperBus 2000
2x20 VFD
Alphanumeric
Touchpad

75 mA

120 mA

60-774 SuperBus 2000

Hardwire Input
Module

18 mA

18 mA

SnapCards (1 per panel)

60-756

4 Input/2 Output
SnapCard

10 mA + 2.5 mA per
zone used
+ 7 mA per smoke
loop used
+ 34 mA per relay
used

185 mA

60-757

8Z Hardwire Input
SnapCard

10 mA + 2.5 mA per
zone used
+ 7 mA per smoke
loop used

230 mA

60-758

4 Output SnapCard

6 mA
+ 34 mA per relay
used

130 mA

Total Standby Current Draw (must not exceed 90 mA
for UL systems)

Total Maximum Current Draw (must not exceed 750 mA)

Note

: For UL listed systems, the difference between the standby current draw and the maximum

current draw of each device must be subtracted from the UL allowed alarm load of 650 mA (panel
terminal 7—OUT1/+12)