Interlogix Concord Express Installation Manual User Manual

Page 69

Advertising
background image

Chapter 2

Concord Express Installation Instructions

63

Smoke Verify (0900)

Onboard Options-Inputs (Default=off)

This setting controls the number of sensor group 26
(fire) zone trips needed to report a fire alarm.

Hardwire Smokes: will determine whether or
not the panel requires two alarm signals within
five minutes (on) from 2-wire smoke detectors
connected to panel zone input 6 and/or
SnapCard zone inputs or any other hardwire
zone learned into group 26 (fire) before
activating system sirens and reporting to a
central station (or pager).

Wireless Smokes: the first trip of a group 26 RF
sensor will cause a local fire alarm. The second
trip of any group 26 zone within the siren
timeout will cause that fire alarm to be reported
to the central station.

Note

: RF smoke detectors repeat the alarm

transmission every 60 seconds as long as they are
detecting smoke. This repeated transmission will
serve as the second zone trip, causing the alarm to
be reported.

To turn Smoke Verify off or on:

1. With the display showing ONBOARD

OPTIONS, press # twice. The display shows
SMOKE VERIFY OFF/ON (current setting).

2. Press 1 (off) or 2 (on). The display flashes the

entered number. Press # and the display
shows the new setting.

Note

: For California State Fire Marshall Listed

installations, this feature must be off.

Two-Wire Smoke (0901)

Onboard Options-Inputs (Default=off)

This setting determines whether panel zone input 6
is set up for 2-wire smoke detectors (on) or for
standard intrusion or 4-wire smoke detectors (off).

Note

: If 2-wire smoke detectors are connected to

hardwire zone input 6, this setting must be turned
on before entering the LEARN SENSORS menu.

To turn Two-Wire Smoke off or on:

1. With the display showing ONBOARD

OPTIONS, press # twice, then B once. The
display shows TWO WIRE SMOKE OFF/ON
(current setting).

2. Press 1 (off) or 2 (on). The display flashes the

entered number. Press # and the display
shows the new setting.

Advertising