2 signal states, 4function description, 3 control element – Pilz PMCprimo DriveP.01/AA0/4/0/0/208-480VAC User Manual
Page 48
![background image](/files/762797/content/doc048.png)
4.3
Control element
4
Function Description
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-16
4.3.3.2
Signal states
Signal states
4-
][Funktion_STO_Signale
If the safety function STO is not required, 24 VDC must always be con-
nected to the inputs STO1-ENABLE and STO2-ENABLE.
Status conditions of the servo amplifier when using STO1-ENABLE and
STO2-ENABLE:
The safety function STO may only be activated once the motor has
stopped rotating (setpoint = 0 V, speed = 0 min
-1
, input ENABLE (X3B/
1) = 0 V).
The following sequence must be maintained if the drive is to use con-
trolled braking:
1. Controlled braking of the drive (speed setpoint = 0 V)
2. Disable the servo amplifier if speed = 0 min
-1
(ENABLE = 0 V)
3. If a suspended load is present, use an additional mechanical measure
to block the drive
4. Activate safety function STO (STO1-ENABLE and STO2-ENABLE=
0 V)
STO1-ENABLE
STO2-ENABLE
ENABLE
Message on display
Motor torque
0 V
0 V
-S-
No
0 V
24 V
F27
No
24 V
0 V
Device ID, e.g. B. 06
No
24 V
24 V
Device ID, e.g. E06
Yes