4.3

Control element

4

Function Description

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-16

4.3.3.2

Signal states

Signal states

4-

][Funktion_STO_Signale

If the safety function STO is not required, 24 VDC must always be con-

nected to the inputs STO1-ENABLE and STO2-ENABLE.

Status conditions of the servo amplifier when using STO1-ENABLE and

STO2-ENABLE:

The safety function STO may only be activated once the motor has

stopped rotating (setpoint = 0 V, speed = 0 min

-1

, input ENABLE (X3B/

1) = 0 V).

The following sequence must be maintained if the drive is to use con-

trolled braking:

1. Controlled braking of the drive (speed setpoint = 0 V)

2. Disable the servo amplifier if speed = 0 min

-1

(ENABLE = 0 V)

3. If a suspended load is present, use an additional mechanical measure

to block the drive

4. Activate safety function STO (STO1-ENABLE and STO2-ENABLE=

0 V)

STO1-ENABLE
STO2-ENABLE

ENABLE

Message on display

Motor torque

0 V

0 V

-S-

No

0 V

24 V

F27

No

24 V

0 V

Device ID, e.g. B. 06

No

24 V

24 V

Device ID, e.g. E06

Yes

Advertising
This manual is related to the following products:

PMCprimo DriveP.01/AA0/5/0/0/208-480VAC, PMCprimo DriveP.12/AA0/4/0/0/208-480VAC, PMCprimo DriveP.12/AA0/4/P/0/208-480VAC, PMCprimo DriveP.03/AA0/4/0/0/208-480VAC, PMCprimo DriveP.06/AA0/4/0/0/208-480VAC, PMCprimo DriveP.24/ABB/4/0/0/208-480VAC, PMCprimo DriveP.03/AB0/5/0/0/208-480VAC, PMCprimo DriveP.06/AB0/2/0/0/208-480VAC, PMCprimo DriveP.03/AB0/3/0/0/208-480VAC, PMCprimo DriveP.06/AB0/3/0/0/208-480VAC, PMCprimo DriveP.12/AB0/2/0/0/208-480VAC, PMCprimo DriveP.12/ABC/4/P/0/208-480VAC, PMCprimo DriveP.12/AB0/3/0/0/208-480VAC, PMCprimo DriveP.03/AB0/2/0/0/208-480VAC, PMCprimo DriveP.12/AAC/4/0/0/208-480VAC, PMCprimo DriveP.24/AA0/5/0/0/208-480VAC, PMCprimo DriveP.12/AA0/2/0/0/208-480VAC, PMCprotego D.01/000/0/0/2/208-480VAC, PMCprotego D.03/000/0/0/2/208-480VAC, PMCprotego D.06/000/0/0/2/208-480VAC, PMCprotego D.12/000/0/0/2/208-480VAC, PMCprotego D.24/000/0/0/2/208-480VAC, PMCprotego D.12/000/0/P/2/208-480VAC, PMCprotego D.24/000/0/P/2/208-480VAC, PMCprotego D.01/200/0/0/2/208-480VAC, PMCprotego D.01/100/0/0/2/208-480VAC, PMCprotego D.01/010/0/0/2/208-480VAC, PMCprotego D.06/010/0/0/2/208-480VAC, PMCprotego D.06/100/0/0/2/208-480VAC, PMCprotego D.06/200/0/0/2/208-480VAC, PMCprotego D.03/010/0/0/2/208-480VAC, PMCprotego D.03/200/0/0/2/208-480VAC, PMCprotego D.03/100/0/0/2/208-480VAC, PMCprotego D.12/010/0/0/2/208-480VAC, PMCprotego D.24/200/0/P/2/208-480VAC, PMCprotego D.12/200/0/0/2/208-480VAC, PMCprotego D.12/100/0/0/2/208-480VAC, PMCprotego D.12/010/0/P/2/208-480VAC, PMCprotego D.12/200/0/P/2/208-480VAC, PMCprotego D.24/100/0/P/2/208-480VAC, PMCprotego D.24/010/0/P/2/208-480VAC, PMCprotego D.12/100/0/P/2/208-480VAC, PMCprotego D.24/200/0/0/2/208-480VAC, PMCprotego D.24/100/0/0/2/208-480VAC, PMCprotego D.24/010/0/0/2/208-480VAC