SiteSync IQ Installation Manual

Wired Signal Circuit Option

Wired Signal Circuit Installation

Glossary

Appendix

Tr

oubleshooting

Clock

Installation

System Contr

oller

Installation

Intr

oduction

To install wired signal circuits (for electrical device control including bells, tone generators, lights, etc.):
1. Disconnect and lock out power to the SiteSync IQ System Controller and any circuit wiring.
2. Remove the top cover from the System Controller.
a. Remove screws from each side of the cover.
b. Slide the cover up off the base of the unit.
3. Route signal circuit wires into the wiring compartment of the System Controller.
a. Remove knockout(s). See Appendix G for illustration showing knockout locations on the rear side of the unit.
b. Use copper conductors only.
c. Use strain relief connector fittings in the knockout holes to secure the wires.
d. Route the wires into the wiring compartment, leaving enough slack to make all connections to the relay terminals.
4. Connect signal wires to the circuit relay terminals.
a. Route the power (feed) line of each circuit to the COM terminal of the desired circuit (1-6) being connected.
b. Route the switched (load) line of each circuit to the NO terminal of the desired circuit (1-6) being connected.
c. Label the wires for each circuit as desired.

n

Note:

The signal circuits are protected with surge suppression components. In some applications, this protection can cause

leakage current to trigger the output device(s) when the circuit is switched ON. In these cases, the surge protection switches (see

illustration below) can be moved to the OFF position. Contact American Time Technical Support with any questions at

800-328-8996.

REAR OF SY

STEM C

ONTR

OLLER

1

2

3

4

5

6

NO

COM

NO

COM

COM

NO

COM

NO

NO

COM

NO

COM

SOURCE

220vac

FUSED

WHITE

BLACK

STEP DOWN

TRANSFORMER

LOW VOLTAGE

DEVICES

POWER

Bell 1

Bell 2

Bell 3

Bell 4

Bell 5

Bell 6

n

IMPORTANT NOTE:

Relay 6 will

be inoperable for running events

when the SiteSync IQ System

Controller is being used to provide

contact closure synchronization

(Tx mode).

Relays

Relay Indicator LEDs

Surge Protection

Switches

Left side

SiteSync IQ System Controller Wiring Compartment Diagram

Typical Signal Circuit

Wiring Diagram

Rear of System Contr

oller

= bell

= light

MON MAR 10 2014
10:38:06 AM USCT
American Time
Status=AUTO ETH=Y