Basler Electric BE1-11 Modbus Protocol User Manual

Page 100

Advertising
background image

94

9424200774 Rev B

Register Table

BE1-11

Name

Description

Group Register

Type

Bytes Writable

Unit

Range

Style

51-7

Mode

SG0

22182
4860*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIT

51-7

Source

SG0

22184

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIT

51-7

Pickup

SG0

22186
4862*

Float

4

R W

Amp

0.5 - 16

FGIT

51-7

Curve Index

SG0

22188
4864*

Uint32

4

R W

n/a

S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13,
C=14, G=15, F=16,
46=17, P=18, T1=19,
T2=20, T3=21, T4=22,
A1=23, B1=24, C1=25,
D1=26, E3=27, F1=28

FGIT

51-7

Direction

SG0

22190
4866*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

51-7

Use
Instantaneous
Reset

SG0

22092
4868*

Uint32

4

R W

n/a

Integrating=0
Instantaneous=1

FGIT

51-7

Constant TD

SG0

22194
4870*

Float

4

R W

n/a

0 - 9.9

FGIT

51-7

Constant A

SG0

22196
4872*

Float

4

R W

n/a

0 - 600

FGIT

51-7

Constant B

SG0

22198
4874*

Float

4

R W

n/a

0 - 25

FGIT

51-7

Constant C

SG0

22200
4876*

Float

4

R W

n/a

0 - 1

FGIT

51-7

Constant N

SG0

22202
4878*

Float

4

R W

n/a

0.5 - 2.5

FGIT

51-7

Constant R

SG0

22204
4880*

Float

4

R W

n/a

0 - 30

FGIT

51-7

Voltage
Restraint
Setpoint

SG0

22206
4882*

Float

4

R W

Volt

30 - 250

FGIT

51-7

Voltage
Restraint
Mode

SG0

22208
4884*

Uint32

4

R W

n/a

Disabled=0
Control=1
Restraint=2

FGIT

51-7

Mode

SG1

22210
4886*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIT

51-7

Source

SG1

22212

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIT

51-7

Pickup

SG1

22214
4888*

Float

4

R W

Amp

0.5 - 16

FGIT

51-7

Curve Index

SG1

22216
4890*

Uint32

4

R W

n/a

S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13,
C=14, G=15, F=16,
46=17, P=18, T1=19,
T2=20, T3=21, T4=22,
A1=23, B1=24, C1=25,
D1=26, E3=27, F1=28

FGIT

51-7

Direction

SG1

22218
4892*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

51-7

Use
Instantaneous
Reset

SG1

22220
4894*

Uint32

4

R W

n/a

Integrating=0
Instantaneous=1

FGIT

51-7

Constant TD

SG1

22222
4896*

Float

4

R W

n/a

0 - 9.9

FGIT

51-7

Constant A

SG1

22224
4898*

Float

4

R W

n/a

0 - 600

FGIT

Advertising