Basler Electric BE1-11 Modbus Protocol User Manual

Page 76

Advertising
background image

70

9424200774 Rev B

Register Table

BE1-11

Name

Description

Group Register

Type

Bytes Writable

Unit

Range

Style

59X-1

Time Multiplier

SG0

21026
3868*

Float

4

R W

n/a

0 - 9.9

FGIMT

59X-1

Mode

SG1

21028
3870*

Uint32

4

R W

n/a

Disabled=0
3V0=1
V1=2
V2=3
Vx Fundamental=4
Vx 3rd Harmonic=5

FGIMT

Reserved

21030-
33

59X-1

Timing Mode

SG1

21034
3872*

Uint32

4

R W

n/a

Definite Timing=0
Inverse Timing=1

FGIMT

59X-1

Pickup

SG1

21036
3874*

Float

4

R W

Volt

1 - 150

FGIMT

59X-1

Time Delay

SG1

21038
3876*

Float

4

R W

Millisecond 50 - 600000

FGIMT

59X-1

Time Multiplier

SG1

21040
3878*

Float

4

R W

n/a

0 - 9.9

FGIMT

59X-1

Mode

SG2

21042
3880*

Uint32

4

R W

n/a

Disabled=0
3V0=1
V1=2
V2=3
Vx Fundamental=4
Vx 3rd Harmonic=5

FGIMT

Reserved

21044-
47

59X-1

Timing Mode

SG2

21048
3882*

Uint32

4

R W

n/a

Definite Timing=0
Inverse Timing=1

FGIMT

59X-1

Pickup

SG2

21050
3884*

Float

4

R W

Volt

1 - 150

FGIMT

59X-1

Time Delay

SG2

21052
3886*

Float

4

R W

Millisecond 50 - 600000

FGIMT

59X-1

Time Multiplier

SG2

21054
3888*

Float

4

R W

n/a

0 - 9.9

FGIMT

59X-1

Mode

SG3

21056
3890*

Uint32

4

R W

n/a

Disabled=0
3V0=1
V1=2
V2=3 Vx Fundamental=4
Vx 3rd Harmonic=5

FGIMT

Reserved

21058-
61

59X-1

Timing Mode

SG3

21062
3892*

Uint32

4

R W

n/a

Definite Timing=0
Inverse Timing=1

FGIMT

59X-1

Pickup

SG3

21064
3894*

Float

4

R W

Volt

1 - 150

FGIMT

59X-1

Time Delay

SG3

21066
3896*

Float

4

R W

Millisecond 50 - 600000

FGIMT

59X-1

Time Multiplier

SG3

21068
3898*

Float

4

R W

n/a

0 - 9.9

FGIMT

59X-2

Mode

SG0

21070
3900*

Uint32

4

R W

n/a

Disabled=0
3V0=1
V1=2
V2=3
Vx Fundamental=4
Vx 3rd Harmonic=5

FGIMT

Reserved

21072-
75

59X-2

Timing Mode

SG0

21076
3902*

Uint32

4

R W

n/a

Definite Timing=0
Inverse Timing=1

FGIMT

59X-2

Pickup

SG0

21078
3904*

Float

4

R W

Volt

1 - 150

FGIMT

59X-2

Time Delay

SG0

21080
3906*

Float

4

R W

Millisecond 50 - 600000

FGIMT

59X-2

Time Multiplier

SG0

21082
3908*

Float

4

R W

n/a

0 - 9.9

FGIMT

59X-2

Mode

SG1

21084
3910*

Uint32

4

R W

n/a

Disabled=0
3V0=1
V1=2
V2=3
Vx Fundamental=4
Vx 3rd Harmonic=5

FGIMT

Reserved

21086-
89

59X-2

Timing Mode

SG1

21090
3912*

Uint32

4

R W

n/a

Definite Timing=0
Inverse Timing=1

FGIMT

59X-2

Pickup

SG1

21092
3914*

Float

4

R W

Volt

1 - 150

FGIMT

59X-2

Time Delay

SG1

21094
3916*

Float

4

R W

Millisecond 50 - 600000

FGIMT

Advertising