Alarms and targets reporting – Basler Electric BE1-11 Modbus Protocol User Manual

Page 161

Advertising
background image

9424200774 Rev B

155

Alarms and Targets Reporting

Alarm and target information is obtained by reading the appropriate register. If an alarm or target is
present, the register will return numeric a value. In a case where more than one alarm or target is present,
you must repeat reading of the register until a value of zero (0) is returned.

Table 5 lists the reporting registers. Table 6 provides a list of possible alarms and targets reported by
these registers.

Table 5. Reporting Registers

Name

Description

Register

Type

Bytes

Major Alarm

Read Alarms

1206

Uint32

4

Minor Alarm

Read Alarms

1208

Uint32

4

Targets

Read Targets

1210

Uint32

4

Relay Alarms

Read Alarms

1212

Uint32

4

Logic Alarms

Read Alarms

1214

Uint32

4

Table 6. Alarms and Targets

Index

Description

64

60FL Alarm

69

60FL Target

99

24 Target

100

24 Alarm

163

27-1 Target A

164

27-1 Target B

165

27-1 Target C

195

27-2 Target A

196

27-2 Target B

197

27-2 Target C

227

27-3 Target A

228

27-3 Target B

229

27-3 Target C

259

27-4 Target A

260

27-4 Target B

261

27-4 Target C

291

27-5 Target A

292

27-5 Target B

293

27-5 Target C

323

27X-1 Target 3V0

324

27X-1 Target V2

325

27X-1 Target Aux

326

27X-1 Target Vx 3rd Harmonic

327

27X-1 Target V1

355

27X-2 Target 3V0

356

27X-2 Target V2

357

27X-2 Target Aux

358

27X-2 Target Vx 3rd Harmonic

BE1-11

Alarms and Targets Reporting