BE1-11

Register Table

Name

Description

Group Register

Type

Bytes Writable

Unit

Range

Style

50-4

Mode

SG1

21400
4148*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIMT

50-4

Source

SG1

21402

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-4

Pickup

SG1

21404
4150*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-4

Time Delay

SG1

21406
4152*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-4

Direction

SG1

21408
4154*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

50-4

Mode

SG2

21410
4156*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIMT

50-4

Source

SG2

21412

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-4

Pickup

SG2

21414
4158*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-4

Time Delay

SG2

21416
4160*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-4

Direction

SG2

21418
4162*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

50-4

Mode

SG3

21420
4164*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIMT

50-4

Source

SG3

21422

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-4

Pickup

SG3

21424
4166*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-4

Time Delay

SG3

21426
4168*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-4

Direction

SG3

21428
4170*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

50-5

Mode

SG0

21430
4172*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIMT

50-5

Source

SG0

21432

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-5

Pickup

SG0

21434
4174*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-5

Time Delay

SG0

21436
4176*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-5

Direction

SG0

21438
4178*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT