Basler Electric BE1-11 Modbus Protocol User Manual

Page 109

Advertising
background image

9424200774 Rev B

103

BE1-11

Register Table

Name

Description

Group Register

Type

Bytes Writable

Unit

Range

Style

81-3

Over
Frequency

SG3

22702
5340*

Float

4

R W

Hertz

15 - 70

FGIMT

81-3

Under
Frequency

SG3

22704
5342*

Float

4

R W

Hertz

15 - 70

FGIMT

81-4

Mode

SG0

22706
5344*

Uint32

4

R W

n/a

Disabled=0
Over=1
Under=2
Rate of Change=3
Positive Rate of
Change=4
Negative Rate of
Change=5

FGIMT

81-4

Pickup

SG0

22708
5346*

Float

4

R W

Hertz

15 - 70

FGIMT

81-4

Time Delay

SG0

22710
5348*

Float

4

R W

Millisecond 0 - 600000

FGIMT

81-4

Voltage Inhibit

SG0

22712
5350*

Float

4

R W

Volt

15 - 250

FGIMT

81-4

Negative
Sequence
Inhibit

SG0

22714
5352*

Float

4

R W

Percent

0 - 99

FGIMT

81-4

Over
Frequency

SG0

22716
5354*

Float

4

R W

Hertz

15 - 70

FGIMT

81-4

Under
Frequency

SG0

22718
5356*

Float

4

R W

Hertz

15 - 70

FGIMT

81-4

Mode

SG1

22720
5358*

Uint32

4

R W

n/a

Disabled=0
Over=1
Under=2
Rate of Change=3
Positive Rate of
Change=4
Negative Rate of
Change=5

FGIMT

81-4

Pickup

SG1

22722
5360*

Float

4

R W

Hertz

15 - 70

FGIMT

81-4

Time Delay

SG1

22724
5362*

Float

4

R W

Millisecond 0 - 600000

FGIMT

81-4

Voltage Inhibit

SG1

22726
5364*

Float

4

R W

Volt

15 - 250

FGIMT

81-4

Negative
Sequence
Inhibit

SG1

22728
5366*

Float

4

R W

Percent

0 - 99

FGIMT

81-4

Over
Frequency

SG1

22730
5368*

Float

4

R W

Hertz

15 - 70

FGIMT

81-4

Under
Frequency

SG1

22732
5370*

Float

4

R W

Hertz

15 - 70

FGIMT

81-4

Mode

SG2

22734
5372*

Uint32

4

R W

n/a

Disabled=0
Over=1
Under=2
Rate of Change=3
Positive Rate of
Change=4
Negative Rate of
Change=5

FGIMT

81-4

Pickup

SG2

22736
5374*

Float

4

R W

Hertz

15 - 70

FGIMT

81-4

Time Delay

SG2

22738
5376*

Float

4

R W

Millisecond 0 - 600000

FGIMT

81-4

Voltage Inhibit

SG2

22740
5378*

Float

4

R W

Volt

15 - 250

FGIMT

81-4

Negative
Sequence
Inhibit

SG2

22742
5380*

Float

4

R W

Percent

0 - 99

FGIMT

81-4

Over
Frequency

SG2

22744
5382*

Float

4

R W

Hertz

15 - 70

FGIMT

81-4

Under
Frequency

SG2

22746
5384*

Float

4

R W

Hertz

15 - 70

FGIMT

81-4

Mode

SG3

22748
5386*

Uint32

4

R W

n/a

Disabled=0
Over=1
Under=2
Rate of Change=3
Positive Rate of
Change=4
Negative Rate of
Change=5

FGIMT

81-4

Pickup

SG3

22750
5388*

Float

4

R W

Hertz

15 - 70

FGIMT

81-4

Time Delay

SG3

22752
5390*

Float

4

R W

Millisecond 0 - 600000

FGIMT

81-4

Voltage Inhibit

SG3

22754
5392*

Float

4

R W

Volt

15 - 250

FGIMT

Advertising