Basler Electric BE1-11 Modbus Protocol User Manual

Page 139

Advertising
background image

9424200774 Rev B

133

BE1-11

Register Table

Name

Description

Group Register

Type

Bytes Writable

Unit

Range

Style

49TC

Max
Emergency
Thermal
Capacity

SG3

24552

Float

4

R W

Percent

150 - 1000

M

49TC

Overload

SG3

24554

Float

4

R W

n/a

0.9 - 1.2

M

50-7

Mode

SG0

24556

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

T

50-7

Source

SG0

24558

Uint32

4

R W

n/a

CT1=0
CT2=1

T

50-7

Pickup

SG0

24560

Float

4

R W

Amp

0.5 - 150

T

50-7

Time Delay

SG0

24562

Float

4

R W

Millisecond 0 - 60000

T

50-7

Direction

SG0

24564

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

T

50-7

Mode

SG1

24566

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

T

50-7

Source

SG1

24568

Uint32

4

R W

n/a

CT1=0
CT2=1

T

50-7

Pickup

SG1

24570

Float

4

R W

Amp

0.5 - 150

T

50-7

Time Delay

SG1

24572

Float

4

R W

Millisecond 0 - 60000

T

50-7

Direction

SG1

24574

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

T

50-7

Mode

SG2

24576

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

T

50-7

Source

SG2

24578

Uint32

4

R W

n/a

CT1=0
CT2=1

T

50-7

Pickup

SG2

24580

Float

4

R W

Amp

0.5 - 150

T

50-7

Time Delay

SG2

24582

Float

4

R W

Millisecond 0 - 60000

T

50-7

Direction

SG2

24584

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

T

50-7

Mode

SG3

24586

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

T

50-7

Source

SG3

24588

Uint32

4

R W

n/a

CT1=0
CT2=1

T

50-7

Pickup

SG3

24590

Float

4

R W

Amp

0.5 - 150

T

50-7

Time Delay

SG3

24592

Float

4

R W

Millisecond 0 - 60000

T

50-7

Direction

SG3

24594

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

T