Basler Electric BE1-11 Modbus Protocol User Manual

Page 28

Advertising
background image

22

9424200774 Rev B

Register Table

BE1-11

Name

Description

Register

Type

Bytes Writable

Range

Style

79

Shot 2

932 bit 6

Uint16 2

R

True=1 False=0

FI

79

Shot 3

932 bit 7

Uint16 2

R

True=1 False=0

FI

79

Shot 4

932 bit 8

Uint16 2

R

True=1 False=0

FI

79

Reclose Initiate

932 bit 9

Uint16 2

R

True=1 False=0

FI

79

Wait

932 bit 10

Uint16 2

R

True=1 False=0

FI

79

Drive to Lockout

932 bit 11

Uint16 2

R

True=1 False=0

FI

79

Zone Pick Up

932 bit 12

Uint16 2

R

True=1 False=0

FI

79

Zone Trip

932 bit 13

Uint16 2

R

True=1 False=0

FI

50BF

Block

932 bit 14

Uint16 2

R

True=1 False=0

FGIMT

50BF

BFI52

932 bit 15

Uint16 2

R

True=1 False=0

FGIMT

50BF

BFI50

933 bit 0

Uint16 2

R

True=1 False=0

FGIMT

50BF

BFRT

933 bit 1

Uint16 2

R

True=1 False=0

FGIMT

50BF

BFT

933 bit 2

Uint16 2

R

True=1 False=0

FGIMT

50BF

50BF Target

933 bit 3

Uint16 2

R

True=1 False=0

FGIMT

50BF

BFI Alarm

933 bit 4

Uint16 2

R

True=1 False=0

FGIMT

50BF

Current Detected

933 bit 5

Uint16 2

R

True=1 False=0

FGIMT

52

Status

933 bit 6

Uint16 2

R

True=1 False=0

FGIMT

52

52 Alarm

933 bit 7

Uint16 2

R

True=1 False=0

FGIMT

Breaker Monitor

Breaker Monitor Block

933 bit 8

Uint16 2

R

True=1 False=0

FGIMT

Demand Meter

IG Demand Alarm

933 bit 9

Uint16 2

R

True=1 False=0

FGIMT

Demand Meter

IN Demand Alarm

933 bit 10

Uint16 2

R

True=1 False=0

FGIMT

Demand Meter

IP Demand Alarm

933 bit 11

Uint16 2

R

True=1 False=0

FGIMT

Demand Meter

IQ Demand Alarm

933 bit 12

Uint16 2

R

True=1 False=0

FGIMT

Demand Meter

Var Positive Demand Alarm

933 bit 13

Uint16 2

R

True=1 False=0

FGIMT

Demand Meter

Var Negative Demand Alarm

933 bit 14

Uint16 2

R

True=1 False=0

FGIMT

Demand Meter

Watt Forward Demand Alarm

933 bit 15

Uint16 2

R

True=1 False=0

FGIMT

Demand Meter

Watt Reverse Demand Alarm

934 bit 0

Uint16 2

R

True=1 False=0

FGIMT

Demand Meter

S Demand Alarm

934 bit 1

Uint16 2

R

True=1 False=0

FGIMT

Local Contacts

Contact Input 1 State

934 bit 2

Uint16 2

R

True=1 False=0

FGIMT

Local Contacts

Contact Input 2 State

934 bit 3

Uint16 2

R

True=1 False=0

FGIMT

Local Contacts

Contact Input 3 State

934 bit 4

Uint16 2

R

True=1 False=0

FGIMT

Local Contacts

Contact Input 4 State

934 bit 5

Uint16 2

R

True=1 False=0

FGIMT

Local Contacts

Contact 52 TCM

934 bit 6

Uint16 2

R

True=1 False=0

FGIMT

Local Contacts

Contact Output 1 State

934 bit 7

Uint16 2

R

True=1 False=0

FGIMT

Local Contacts

Contact Output 2 State

934 bit 8

Uint16 2

R

True=1 False=0

FGIMT

Local Contacts

Contact Output 3 State

934 bit 9

Uint16 2

R

True=1 False=0

FGIMT

Local Contacts

Contact Output 4 State

934 bit 10

Uint16 2

R

True=1 False=0

FGIMT

Local Contacts

Contact Output 5 State

934 bit 11

Uint16 2

R

True=1 False=0

FGIMT

Local Contacts

Contact Output A State

934 bit 12

Uint16 2

R

True=1 False=0

FGIMT

System Data

RF Trigger

934 bit 13

Uint16 2

R

True=1 False=0

FGIMT

System Data

Pickup Logic

934 bit 14

Uint16 2

R

True=1 False=0

FGIMT

System Data

Trip Logic

934 bit 15

Uint16 2

R

True=1 False=0

FGIMT

System Data

Logic Trigger

935 bit 0

Uint16 2

R

True=1 False=0

FGIMT

System Data

Breaker Status

935 bit 1

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Flash Failure Alarm

935 bit 2

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Micro Failure Alarm

935 bit 3

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Calibration Error Alarm

935 bit 4

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Calibration Defaults Alarm

935 bit 5

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Defaults Loaded Alarm

935 bit 6

Uint16 2

R

True=1 False=0

FGIMT

Alarms

System Overload Alarm

935 bit 7

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Power Supply Alarm

935 bit 8

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Changes Lost Alarm

935 bit 9

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Real-Time Clock Alarm

935 bit 10

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Date/Time Set Alarm

935 bit 11

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Firmware Changed Alarm

935 bit 12

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Frequency Out of Range Alarm

935 bit 13

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Ethernet Link Lost Alarm

935 bit 14

Uint16 2

R

True=1 False=0

FGIMT

Reserved

935 bit 15

Alarms

IRIG Sync Lost Alarm

936 bit 0

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Logic = None Alarm

936 bit 1

Uint16 2

R

True=1 False=0

FGIMT

Alarms

No User Setting Alarm

936 bit 2

Uint16 2

R

True=1 False=0

FGIMT

Alarms

NTP Sync Lost Alarm

936 bit 3

Uint16 2

R

True=1 False=0

FGIMT

Alarms

DNP Polls Error

936 bit 4

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Setting Change Alarm

936 bit 5

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Output Override Alarm

936 bit 6

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Analog Alarm

936 bit 7

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Microprocessor Reset Alarm

936 bit 8

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Breaker Monitor 1

936 bit 9

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Breaker Monitor 2

936 bit 10

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Breaker Monitor 3

936 bit 11

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Fault Report Timeout

936 bit 12

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Programmable Alarm 1

936 bit 13

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Programmable Alarm 2

936 bit 14

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Programmable Alarm 3

936 bit 15

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Programmable Alarm 4

937 bit 0

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Programmable Alarm 5

937 bit 1

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Programmable Alarm 6

937 bit 2

Uint16 2

R

True=1 False=0

FGIMT

Alarms

Programmable Alarm 7

937 bit 3

Uint16 2

R

True=1 False=0

FGIMT

Advertising