Basler Electric BE1-11 Modbus Protocol User Manual

Page 130

Advertising
background image

124

9424200774 Rev B

Register Table

BE1-11

Name

Description

Group Register

Type

Bytes Writable

Unit

Range

Style

Analog Input Protection 8

Pickup

SG3

23912

Float

4

R W

n/a

-999999.9 - 999999.9

FGIMT

Analog Input Protection 8

Time Delay

SG3

23914

Float

4

R W

Millisecond 0 - 60000

FGIMT

Analog Input Protection 8

Inhibit Level

SG3

23916

Float

4

R W

n/a

-99999.9 - 99999.9

FGIMT

48

Mode

SG0

23918

Uint32

4

R W

n/a

Disabled=0
Enabled=1

M

48

Time Interval

SG0

23920

Float

4

R W

Second

0 - 600

M

48

Mode

SG1

23922

Uint32

4

R W

n/a

Disabled=0
Enabled=1

M

48

Time Interval

SG1

23924

Float

4

R W

Second

0 - 600

M

48

Mode

SG2

23926

Uint32

4

R W

n/a

Disabled=0
Enabled=1

M

48

Time Interval

SG2

23928

Float

4

R W

Second

0 - 600

M

48

Mode

SG3

23930

Uint32

4

R W

n/a

Disabled=0
Enabled=1

M

48

Time Interval

SG3

23932

Float

4

R W

Second

0 - 600

M

66-1

Mode

SG0

23934

Uint32

4

R W

n/a

Disabled=0
Enabled=1

M

66-1

Time Interval

SG0

23936

Uint32

4

R W

Minute

1 - 1440

M

66-1

Number Of
Starts

SG0

23938

Uint32

4

R W

n/a

1 - 100

M

66-1

Mode

SG1

23940

Uint32

4

R W

n/a

Disabled=0
Enabled=1

M

66-1

Time Interval

SG1

23942

Uint32

4

R W

Minute

1 - 1440

M

66-1

Number Of
Starts

SG1

23944

Uint32

4

R W

n/a

1 - 100

M

66-1

Mode

SG2

23946

Uint32

4

R W

n/a

Disabled=0
Enabled=1

M

66-1

Time Interval

SG2

23948

Uint32

4

R W

Minute

1 - 1440

M

66-1

Number Of
Starts

SG2

23950

Uint32

4

R W

n/a

1 - 100

M

66-1

Mode

SG3

23952

Uint32

4

R W

n/a

Disabled=0
Enabled=1

M

66-1

Time Interval

SG3

23954

Uint32

4

R W

Minute

1 - 1440

M

66-1

Number Of
Starts

SG3

23956

Uint32

4

R W

n/a

1 - 100

M

Reserved

23958-
61

Restart Inhibit

Restart Delay

SG0

23962

Uint32

4

R W

Minute

0 - 7200

M

Restart Inhibit

Time Between
Starts

SG0

23964

Uint32

4

R W

Minute

0 - 7200

M

Restart Inhibit

Thermal
Capacity
Inhibit

SG0

23966

Float

4

R W

Percent

0 - 70

M

Reserved

23968-
70

Restart Inhibit

Restart Delay

SG1

23972

Uint32

4

R W

Minute

0 - 7200

M

Restart Inhibit

Time Between
Starts

SG1

23974

Uint32

4

R W

Minute

0 - 7200

M

Restart Inhibit

Thermal
Capacity
Inhibit

SG1

23976

Float

4

R W

Percent

0 - 70

M

Reserved

23978-
80

Restart Inhibit

Restart Delay

SG2

23982

Uint32

4

R W

Minute

0 - 7200

M

Restart Inhibit

Time Between
Starts

SG2

23984

Uint32

4

R W

Minute

0 - 7200

M

Restart Inhibit

Thermal
Capacity
Inhibit

SG2

23986

Float

4

R W

Percent

0 - 70

M

Reserved

23988-
90

Restart Inhibit

Restart Delay

SG3

23992

Uint32

4

R W

Minute

0 - 7200

M

Restart Inhibit

Time Between
Starts

SG3

23994

Uint32

4

R W

Minute

0 - 7200

M

Restart Inhibit

Thermal
Capacity
Inhibit

SG3

23996

Float

4

R W

Percent

0 - 70

M

49RTD-1

Mode

SG0

23998

Uint32

4

R W

n/a

Disabled=0
Over=1
Under=2
Over/Under=3

FGIMT

49RTD-1

Source

SG0

24000

Uint32

4

R W

n/a

Configuration Group 1=0
Configuration Group 2=1
Configuration Group 3=2
Configuration Group 4=3
Configuration Group 5=4
Configuration Group 6=5
Configuration Group 7=6

FGIMT

49RTD-1

Over Pickup

SG0

24002

Float

4

R W

Degrees C

0 - 250

FGIMT

49RTD-1

Under Pickup

SG0

24004

Float

4

R W

Degrees C

0 - 250

FGIMT

Advertising