Register Table

Reporting Setup

Name

Description

Register

Type

Bytes

Writable

Major Alarm

Binary Point Number

2700

Uint32

4

R W

Major Alarm

Binary Point State

2702

Uint32

4

R W

Major Alarm

Reset

2704

Uint32

4

R W

Minor Alarm

Binary Point Number

2706

Uint32

4

R W

Minor Alarm

Binary Point State

2708

Uint32

4

R W

Minor Alarm

Reset

2710

Uint32

4

R W

Targets

Binary Point Number

2712

Uint32

4

R W

Targets

Binary Point State

2714

Uint32

4

R W

Targets

Reset

2716

Uint32

4

R W

Relay Alarms

Binary Point Number

2718

Uint32

4

R W

Relay Alarms

Binary Point State

2720

Uint32

4

R W

Relay Alarms

Reset

2722

Uint32

4

R W

Logic Alarms

Binary Point Number

2724

Uint32

4

R W

Logic Alarms

Binary Point State

2726

Uint32

4

R W

Logic Alarms

Reset

2728

Uint32

4

R W

Power Quality Setup

Name

Description

Register

Type

Bytes

Writable

Unit

Range

Power Quality

Reference Mode

2800

Uint32

4

R W

n/a

Fixed=0
Sliding=1

Power Quality

Dip Ratio

2802

Float

4

R W

Ratio

0.7 - 1

Power Quality

Swell Ratio

2804

Float

4

R W

Ratio

1 - 1.3

Power Quality

Dip Hysteresis

2806

Float

4

R W

Ratio

1 - 1.3

Power Quality

Swell Hysteresis

2808

Float

4

R W

Ratio

0.7 - 1

Power Quality

Harmonic to Read

2810

Float

4

R W

n/a

1 - 15

Demand Setup

Name

Description

Register

Type

Bytes

Writable

Unit

Range

Demand Meter

Period-Phase

2900

Float

4

R W

Minute

1 - 60

Demand Meter

Alarm-Threshold Phase

2902

Float

4

R W

Amp

0.5 - 16

Demand Meter

Period-Neutral

2904

Float

4

R W

Minute

1 - 60

Demand Meter

Alarm-Threshold Neutral

2906

Float

4

R W

Amp

0.5 - 16

Demand Meter

Period-I2

2908

Float

4

R W

Minute

1 - 60

Demand Meter

Alarm-Threshold I2

2910

Float

4

R W

Amp

0.5 - 16

Demand Meter

Alarm-Threshold Watt Positive

2912

Float

4

R W

Watt

0 - 8500

Demand Meter

Alarm-Threshold Watt Negative

2914

Float

4

R W

Watt

0 - 8500

Demand Meter

Alarm-Threshold var Positive

2916

Float

4

R W

var

0 - 8500

Demand Meter

Alarm-Threshold var Negative

2918

Float

4

R W

var

0 - 8500

Demand Meter

Alarm-Threshold S

2920

Float

4

R W

VA

0 - 8500

Current Demand Circuit 2

Period-Phase

2922

Float

4

R W

Minute

1 - 60

Current Demand Circuit 2

Alarm-Threshold Phase

2924

Float

4

R W

Amp

0.5 - 16

Current Demand Circuit 2

Period-Neutral

2926

Float

4

R W

Minute

1 - 60

Current Demand Circuit 2

Alarm-Threshold Neutral

2928

Float

4

R W

Amp

0.5 - 16

Current Demand Circuit 2

Period-I2

2930

Float

4

R W

Minute

1 - 60

Current Demand Circuit 2

Alarm-Threshold I2

2932

Float

4

R W

Amp

0.5 - 16

G Current Demand Circuit 2

Period-Neutral

2934

Float

4

R W

Minute

1 - 60

G Current Demand Circuit 2

Alarm-Threshold Neutral

2936

Float

4

R W

Amp

0.5 - 16

Fault Record Setup

Name

Description

Register

Type

Bytes

Writable

Range

Fault Report Selection

Record-Selection

3000

Int32

4

R W

1 - 255

Fault Report

Reset

3002

Uint32

4

R W

n/a

Poll Block Settings

Name

Description

Register

Type

Bytes

Writable

Range

Modbus

DB key For MB Polling Block Register 1

9676

Uint16

2

R

1 - 9874

Modbus

DB key For MB Polling Block Register 2

9677

Uint16

2

R

1 - 9874

Modbus

DB key For MB Polling Block Register 3

9678

Uint16

2

R

1 - 9874

Modbus

DB key For MB Polling Block Register 4

9679

Uint16

2

R

1 - 9874

Modbus

DB key For MB Polling Block Register 5

9680

Uint16

2

R

1 - 9874

Modbus

DB key For MB Polling Block Register 6

9681

Uint16

2

R

1 - 9874

Modbus

DB key For MB Polling Block Register 7

9682

Uint16

2

R

1 - 9874

Modbus

DB key For MB Polling Block Register 8

9683

Uint16

2

R

1 - 9874

Modbus

DB key For MB Polling Block Register 9

9684

Uint16

2

R

1 - 9874

Modbus

DB key For MB Polling Block Register 10

9685

Uint16

2

R

1 - 9874

Modbus

DB key For MB Polling Block Register 11

9686

Uint16

2

R

1 - 9874

Modbus

DB key For MB Polling Block Register 12

9687

Uint16

2

R

1 - 9874

Modbus

DB key For MB Polling Block Register 13

9688

Uint16

2

R

1 - 9874

Modbus

DB key For MB Polling Block Register 14

9689

Uint16

2

R

1 - 9874

Modbus

DB key For MB Polling Block Register 15

9690

Uint16

2

R

1 - 9874