Message framing and timing considerations, Modbus™ on tcp/ip, Application data unit – Basler Electric BE1-11 Modbus Protocol User Manual

Page 9: Modbus ™ on tcp/ip

Advertising
background image

9424200774 Rev B

3

installation and altered during real-time operation. The BE1-11 Modbus supports baud rates up to
115200. The factory default baud rate is 19200.

The BE1-11 supports RS-485 compatible serial interfaces. This interface is accessible from the rear panel
of the BE1-11. The RS-485 interface is configured for Modbus communication when Option “M” is
ordered.

Message Framing and Timing Considerations

When receiving a message via the RS-485 communication port, the BE1-11 requires an inter-byte latency
of 3.5 character times before considering the message complete.

Once a valid query is received, the BE1-11 waits a specified amount of time before responding. This time
delay is set on the Miscellaneous Modbus Settings screen under Communications in BESTCOMSPlus

®.

This parameter contains a value from 10 - 10,000 milliseconds. The default value is 10 milliseconds.

Table 1 provides the response message transmission time (in seconds) and 3.5 character times (in
milliseconds) for various message lengths and baud rates.

Table 1. Timing Considerations

Baud Rate

3.5 Character Time (ms)

Message Tx Time (s)

128 Bytes

256 Bytes

2400

16.04

0.59

1.17

4800

8.021

0.29

0.59

9600

4.0104

0.15

0.29

19200

2.0052

0.07

0.15

Modbus

™ on TCP/IP

Application Data Unit

The following describes the encapsulation of a Modbus request or response when it is carried on a
Modbus TCP/IP network. See Figure 2.

Figure 2. Modbus Request/Response Over TCP/IP

A dedicated header is used on TCP/IP to identify the Modbus Application Data Unit. It is called the MBAP
header (Modbus Application Protocol header).

This header provides some differences compared to the Modbus RTU application data unit used on a
serial line:

The Modbus ‘slave address’ field usually used on Modbus Serial Line is replaced by a single byte
‘Unit Identifier’ within the MBAP header. The ‘Unit Identifier’ is used to communicate via devices
such as bridges, routers, and gateways that use a single IP address to support multiple
independent Modbus end units.

All Modbus requests and responses are designed in such a way that the recipient can verify that
a message is finished. For function codes where the Modbus PDU has a fixed length, the function
code alone is sufficient. For function codes carrying a variable amount of data in the request or
response, the data field includes a byte count.

PDU

Modbus TCP/IP ADU

Function code

Data

MBAP Header

BE1-11

General Information