Basler Electric BE1-11 Modbus Protocol User Manual

Page 80

Advertising
background image

74

9424200774 Rev B

Register Table

BE1-11

Name

Description

Group Register

Type

Bytes Writable

Unit

Range

Style

50-1

Mode

SG1

21280
4052*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8

FGIMT

50-1

Source

SG1

21282

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-1

Pickup

SG1

21284
4054*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-1

Time Delay

SG1

21286
4056*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-1

Direction

SG1

21288
4058*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

50-1

Mode

SG2

21290
4060*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIMT

50-1

Source

SG2

21292

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-1

Pickup

SG2

21294
4062*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-1

Time Delay

SG2

21296
4064*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-1

Direction

SG2

21298
4066*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

50-1

Mode

SG3

21300
4068*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIMT

50-1

Source

SG3

21302

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-1

Pickup

SG3

21304
4070*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-1

Time Delay

SG3

21306
4072*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-1

Direction

SG3

21308
4074*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

50-2

Mode

SG0

21310
4076*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIMT

50-2

Source

SG0

21312

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-2

Pickup

SG0

21314
4078*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-2

Time Delay

SG0

21316
4080*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-2

Direction

SG0

21318
4082*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

Advertising