Global settings – Basler Electric BE1-11 Modbus Protocol User Manual

Page 50

Advertising
background image

44

9424200774 Rev B

Register Table

BE1-11

Name

Description

Register

Type

Bytes

Writable

Unit

Range

Current Demand Circuit 2

3I0 Peak

12516

Float

4

R

Amp

0 - 2000000000

Current Demand Circuit 2

I2 Peak

12518

Float

4

R

Amp

0 - 2000000000

Current Demand Circuit 2

IA Peak Time

12520

String

24

R

n/a

n/a

Current Demand Circuit 2

IB Peak Time

12532

String

24

R

n/a

n/a

Current Demand Circuit 2

IC Peak Time

12544

String

24

R

n/a

n/a

Current Demand Circuit 2

3I0 Peak Time

12556

String

24

R

n/a

n/a

Current Demand Circuit 2

I2 Peak Time

12568

String

24

R

n/a

n/a

G Current Demand Circuit 2

IG Present

12580

Float

4

R

Amp

0 - 2000000000

G Current Demand Circuit 2

IG Peak

12582

Float

4

R

Amp

0 - 2000000000

G Current Demand Circuit 2

IG Peak Time

12584

String

24

R

n/a

n/a

* Legacy register

Global Settings

Name

Description

Register

Type

Bytes Writable

Unit

Range

Style

Phase Bus

Rotation

18100
2400*

Int32

4

R W

n/a

ABC=0
ACB=1

FGIMT

Phase Bus

Phase VT
Connection

18102
2402*

Int32

4

R W

n/a

AB=0
BC=1
CA=2
AN=3
BN=4
CN=5
3W D=7
4W-Y=8

FGIMT

Reserved

18104
2404*

Phase Bus

Phase VT
Ratio

18106
2406*

Float

4

R W

n/a

1 - 10000

FGIMT

Phase Bus 1

Phase CT
Ratio

18108
2408*

Float

4

R W

n/a

1 - 50000

FGIMT

Phase Bus

V rated

18110
2410*

Float

4

R W

Volt

1 - 1000

FGIMT

Phase Bus

I rated

18112
2412*

Float

4

R W

Amp

0 - 15

FGIMT

Reserved

18114-
19
2414-
2419*

Aux Bus

Aux VT
Connection

18120
2420*

Int32

4

R W

AB=0
BC=1
CA=2
AN=3
BN=4
CN=5
Ground=10

FGIMT

Aux Bus

Aux VT Ratio

18122
2422*

Float

4

R W

n/a

1 - 10000

FGIMT

Aux Bus

V rated

18124
2424*

Float

4

R W

Volt

1 - 1000

FGIMT

System
Configure

Nominal
Frequency

18126
2426*

Uint32 4

R W

n/a

25 Hz=25
50 Hz=50
60 Hz=60

FGIMT

Reserved

18128-
37
2428-
2437*

Aux Bus 1

Ground CT
Ratio

18138
2438*

Float

4

R W

n/a

1 - 50000

FGIMT

System
Configure

Phase-To
Phase 2759

18140
2440*

Uint32 4

R W

n/a

PN=0
PP=1

FGIMT

System
Configure

Phase-To
Phase 27R

18142
2442*

Uint32 4

R W

n/a

PN=0
PP=1

FGIMT

60FL

Fuse Loss I
Block Mode

18144
2444*

Uint32 4

R W

n/a

Disabled=0
Enabled=1

FGIMT

60FL

Fuse Loss P
Block Mode

18146
2446*

Uint32 4

R W

n/a

Disabled=0
Enabled=1

FGIMT

60FL

Fuse Loss N
Block Mode

18148
2448*

Uint32 4

R W

n/a

Disabled=0
Enabled=1

FGIMT

60FL

Fuse Loss Q
Block Mode

18150
2450*

Uint32 4

R W

n/a

Disabled=0
Enabled=1

FGIMT

Local
Contacts

Contact Input
1 Recognition
Time

18152
2452*

Uint8

1

R W

Millisecond 4 - 255

FGIMT

Local
Contacts

Contact Input
2 Recognition
Time

18153
2453*

Uint8

1

R W

Millisecond 4 - 255

FGIMT