Basler Electric BE1-11 Modbus Protocol User Manual

Page 81

Advertising
background image

9424200774 Rev B

75

BE1-11

Register Table

Name

Description

Group Register

Type

Bytes Writable

Unit

Range

Style

50-2

Mode

SG1

21320
4084*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIMT

50-2

Source

SG1

21322

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-2

Pickup

SG1

21324
4086*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-2

Time Delay

SG1

21326
4088*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-2

Direction

SG1

21328
4090*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

50-2

Mode

SG2

21330
4092*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIMT

50-2

Source

SG2

21332

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-2

Pickup

SG2

21334
4094*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-2

Time Delay

SG2

21336
4096*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-2

Direction

SG2

21338
4098*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

50-2

Mode

SG3

21340
4100*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIMT

50-2

Source

SG3

21342

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-2

Pickup

SG3

21344
4102*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-2

Time Delay

SG3

21346
4104*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-2

Direction

SG3

21348
4106*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

50-3

Mode

SG0

21350
4108*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIMT

50-3

Source

SG0

21352

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-3

Pickup

SG0

21354
4110*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-3

Time Delay

SG0

21356
4112*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-3

Direction

SG0

21358
4114*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

Advertising