Register Table

Register Table

Parameters are mapped into the holding register address space in blocks according to access type.
Registers 9875 through 9999 are reserved for user configurable polling block, and register 9874 is
reserved for system use only. By default, all registers in the polling block are mapped to register 9874
when their value is zero. Use BESTCOMSPlus

® to map desired data to poll block registers to be read by

one Modbus

™ read request.

Any holding register not listed in the register table is an unassigned holding register. Reading or writing to
unassigned holding registers is not allowed and error code “Illegal Data Address” will be reported.

Reading/Writing any data (variable) as its complete (atomic) value is the only legal operation. Partially
requested data will return an error. For example, request for reading/writing of/to only register 620 will
return an error because this register is part of data Settings Group-Direct Operate that is mapped to 2
registers. Reading of register 620 is correct only if reading/writing of both 620 and 621 are requested in
the same query.

Conventions

The Type column uses the following abbreviations:

String - ASCII string

Float - Floating point

Int32 - Integer (32-bit integer)

Int16 - Integer (16-bit integer)

Int8 - Integer (8-bit integer)

Uint32 - Unsigned Integer (32-bit integer)

Uint16 - Unsigned Integer (16-bit integer)

Uint8 - Unsigned Integer (8-bit integer)

IP Address - IP Address

The Style column uses the following abbreviations:

F - Feeder Protection System

G - Generator Protection System

I - Intertie Protection System

M - Motor Protection System

T - Transformer Protection System

Register Table

The register table on the following pages contains the following groups:

General, SBO Select, SBO Operate, Direct Operate, Binary Points, Reporting, Power Quality, Fault
Record, Relay Settings, Reporting Setup, Power Quality Setup, Demand Setup, Fault Record Setup, Poll
Block Settings, Metering, Demand Data, Global Settings, Protection Settings, and User Labels.

General

Name

Description

Register

Type

Bytes

Writable

Range

System Data

Default Graphics Module Version

1

String

13

R

0 - 13

System Data

Alternate Graphics Module Version

8

String

13

R

0 - 13

System Data

Model Number

15

String

64

R

0 - 64

Reserved

47-110

System Data

Boot Version Information

111

String

64

R

0 - 64

Reserved

143-206

System Data

Firmware Part Number

207

String

64

R

0 - 64

Unit Info

Style Number

239

String

32

R

0 - 32

Unit Info

Model Number

255

String

64

R

0 - 64

Unit Info

App Part Number

287

String

64

R

0 - 64

Unit Info

Serial Number

319

String

32

R

0 - 32