Basler Electric BE1-11 Modbus Protocol User Manual

Page 75

Advertising
background image

9424200774 Rev B

69

BE1-11

Register Table

Name

Description

Group Register

Type

Bytes Writable

Unit

Range

Style

Reserved

20956-
57

59P-3

Timing Mode

SG3

20958
3812*

Uint32

4

R W

n/a

Definite Timing=0
Inverse Timing=1

FGIT

59P-3

Pickup

SG3

20960
3814*

Float

4

R W

Volt

1 - 300

FGIT

59P-3

Time Delay

SG3

20962
3816*

Float

4

R W

Millisecond 50 - 600000

FGIT

59P-3

Time Multiplier

SG3

20964
3818*

Float

4

R W

n/a

0 - 9.9

FGIT

59P-4

Mode

SG0

20966
3820*

Uint32

4

R W

n/a

Disabled=0
One of Three=1
Two of Three=2
Three of Three=3

FGIT

Reserved

20968-
69

59P-4

Timing Mode

SG0

20970
3822*

Uint32

4

R W

n/a

Definite Timing=0
Inverse Timing=1

FGIT

59P-4

Pickup

SG0

20972
3824*

Float

4

R W

Volt

1 - 300

FGIT

59P-4

Time Delay

SG0

20974
3826*

Float

4

R W

Millisecond 50 - 600000

FGIT

59P-4

Time Multiplier

SG0

20976
3828*

Float

4

R W

n/a

0 - 9.9

FGIT

59P-4

Mode

SG1

20978
3830*

Uint32

4

R W

n/a

Disabled=0
One of Three=1
Two of Three=2
Three of Three=3

FGIT

Reserved

20980-
81

59P-4

Timing Mode

SG1

20982
3832*

Uint32

4

R W

n/a

Definite Timing=0
Inverse Timing=1

FGIT

59P-4

Pickup

SG1

20984
3834*

Float

4

R W

Volt

1 - 300

FGIT

59P-4

Time Delay

SG1

20986
3836*

Float

4

R W

Millisecond 50 - 600000

FGIT

59P-4

Time Multiplier

SG1

20988
3838*

Float

4

R W

n/a

0 - 9.9

FGIT

59P-4

Mode

SG2

20990
3840*

Uint32

4

R W

n/a

Disabled=0
One of Three=1
Two of Three=2
Three of Three=3

FGIT

Reserved

20992-
93

59P-4

Timing Mode

SG2

20994
3842*

Uint32

4

R W

n/a

Definite Timing=0
Inverse Timing=1

FGIT

59P-4

Pickup

SG2

20996
3844*

Float

4

R W

Volt

1 - 300

FGIT

59P-4

Time Delay

SG2

20998
3846*

Float

4

R W

Millisecond 50 - 600000

FGIT

59P-4

Time Multiplier

SG2

21000
3848*

Float

4

R W

n/a

0 - 9.9

FGIT

59P-4

Mode

SG3

21002
3850*

Uint32

4

R W

n/a

Disabled=0
One of Three=1
Two of Three=2
Three of Three=3

FGIT

Reserved

21004-
05

59P-4

Timing Mode

SG3

21006
3852*

Uint32

4

R W

n/a

Definite Timing=0
Inverse Timing=1

FGIT

59P-4

Pickup

SG3

21008
3854*

Float

4

R W

Volt

1 - 300

FGIT

59P-4

Time Delay

SG3

21010
3856*

Float

4

R W

Millisecond 50 - 600000

FGIT

59P-4

Time Multiplier

SG3

21012
3858*

Float

4

R W

n/a

0 - 9.9

FGIT

59X-1

Mode

SG0

21014
3860*

Uint32

4

R W

n/a

Disabled=0
3V0=1
V1=2
V2=3
Vx Fundamental=4
Vx 3rd Harmonic=5

FGIT

Reserved

21016-
19

59X-1

Timing Mode

SG0

21020
3862*

Uint32

4

R W

n/a

Definite Timing=0
Inverse Timing=1

FGIMT

59X-1

Pickup

SG0

21022
3864*

Float

4

R W

Volt

1 - 150

FGIMT

59X-1

Time Delay

SG0

21024
3866*

Float

4

R W

Millisecond 50 - 600000

FGIMT

Advertising