Basler Electric BE1-11 Modbus Protocol User Manual

Page 136

Advertising
background image

130

9424200774 Rev B

Register Table

BE1-11

Name

Description

Group Register

Type

Bytes Writable

Unit

Range

Style

87

Source

SG1

24324

Uint32

4

R W

n/a

CT1=0
CT2=1

GMT

87

Min Restrained
Pickup Value

SG1

24326

Float

4

R W

n/a

0.1 - 1

GMT

87

Second
Restrained
Pickup Value

SG1

24328

Float

4

R W

n/a

1 - 20

GMT

87

Restraint
Slope Mode

SG1

24330

Uint32

4

R W

n/a

Maximum=0
Average=1

GMT

87

Restraint
Slope 1

SG1

24332

Float

4

R W

Percent

5 - 100

GMT

87

Restraint
Slope 2

SG1

24334

Float

4

R W

Percent

15 - 140

GMT

87

Alarm Slope

SG1

24336

Float

4

R W

Percent

50 - 100

GMT

Reserved

24338-
39

87

2

nd

Harmonic

Restraint

SG1

24340

Float

4

R W

Percent

0 - 75

GT

87

5

th

Harmonic

SG1

24342

Float

4

R W

Percent

0 - 75

GT

87

Shared
Harmonic
Restraint

SG1

24344

Uint32

4

R W

n/a

Independent=0
Shared=1

GMT

87

Unrestrained
Pickup Mode

SG1

24346

Uint32

4

R W

n/a

Disabled=0
Enabled=1

GMT

87

Unrestrained
Pickup Value

SG1

24348

Float

4

R W

n/a

0 - 21

GMT

87

Flux Balance
Pickup

SG1

24350

Float

4

R W

Amp

0.1 - 5

GMT

87

Flux Balance
Alarm

SG1

24352

Float

4

R W

Amp

0.1 - 5

GMT

87

Mode

SG2

24354

Uint32

4

R W

n/a

Disabled=0
Percent Differential=1
Flux Balance=2

GMT

87

Time Delay

SG2

24356

Float

4

R W

Millisecond 0 - 60000

GMT

87

Source

SG2

24358

Uint32

4

R W

n/a

CT1=0
CT2=1

GMT

87

Min Restrained
Pickup Value

SG2

24360

Float

4

R W

n/a

0.1 - 1

GMT

87

Second
Restrained
Pickup Value

SG2

24362

Float

4

R W

n/a

1 - 20

GMT

87

Restraint
Slope Mode

SG2

24364

Uint32

4

R W

n/a

Maximum=0
Average=1

GMT

87

Restraint
Slope 1

SG2

24366

Float

4

R W

Percent

5 - 100

GMT

87

Restraint
Slope 2

SG2

24368

Float

4

R W

Percent

15 - 140

GMT

87

Alarm Slope

SG2

24370

Float

4

R W

Percent

50 - 100

GMT

Reserved

24372-
73

87

2

nd

Harmonic

Restraint

SG2

24374

Float

4

R W

Percent

0 - 75

GT

87

5

th

Harmonic

SG2

24376

Float

4

R W

Percent

0 - 75

GT

87

Shared
Harmonic
Restraint

SG2

24378

Uint32

4

R W

n/a

Independent=0
Shared=1

GMT

87

Unrestrained
Pickup Mode

SG2

24380

Uint32

4

R W

n/a

Disabled=0
Enabled=1

GMT

87

Unrestrained
Pickup Value

SG2

24382

Float

4

R W

n/a

0 - 21

GMT

87

Flux Balance
Pickup

SG2

24384

Float

4

R W

Amp

0.1 - 5

GMT

87

Flux Balance
Alarm

SG2

24386

Float

4

R W

Amp

0.1 - 5

GMT

87

Mode

SG3

24388

Uint32

4

R W

n/a

Disabled=0
Percent Differential=1
Flux Balance=2

GMT

87

Time Delay

SG3

24390

Float

4

R W

Millisecond 0 - 60000

GMT

87

Source

SG3

24392

Uint32

4

R W

n/a

CT1=0
CT2=1

GMT

87

Min Restrained
Pickup Value

SG3

24394

Float

4

R W

n/a

0.1 - 1

GMT

87

Second
Restrained
Pickup Value

SG3

24396

Float

4

R W

n/a

1 - 20

GMT

87

Restraint
Slope Mode

SG3

24398

Uint32

4

R W

n/a

Maximum=0
Average=1

GMT

87

Restraint
Slope 1

SG3

24400

Float

4

R W

Percent

5 - 100

GMT

Advertising