Basler Electric BE1-11 Modbus Protocol User Manual

Page 55

Advertising
background image

9424200774 Rev B

49

BE1-11

Register Table

Name

Description

Register

Type

Bytes Writable

Unit

Range

Style

Analog Input
Config 4

Type

18374

Uint32 4

R W

n/a

Voltage=0
Current=1

FGIMT

Analog Input
Config 4

Parameter
Minimum

18376

Float

4

R W

n/a

-199999.8

FGIMT

Analog Input
Config 4

Parameter
Maximum

18378

Float

4

R W

n/a

-199999.8

FGIMT

Analog Input
Config 4

Input Current
Minimum

18380

Float

4

R W

Milliamp

4 - 20

FGIMT

Analog Input
Config 4

Input Current
Maximum

18382

Float

4

R W

Milliamp

4 - 20

FGIMT

Analog Input
Config 4

Input Voltage
Minimum

18384

Float

4

R W

Volt

0 - 10

FGIMT

Analog Input
Config 4

Input Voltage
Maximum

18386

Float

4

R W

Volt

0 - 10

FGIMT

Analog Output
Config 1

Type

18388

Uint32 4

R W

n/a

Voltage=0
Current=1

FGIMT

Analog Output
Config 1

Parameter
Minimum

18390

Float

4

R W

n/a

-199999.8

FGIMT

Analog Output
Config 1

Parameter
Maximum

18392

Float

4

R W

n/a

-199999.8

FGIMT

Analog Output
Config 1

Output
Current
Minimum

18394

Float

4

R W

Milliamp

4 - 20

FGIMT

Analog Output
Config 1

Output
Current
Maximum

18396

Float

4

R W

Milliamp

4 - 20

FGIMT

Analog Output
Config 1

Output
Voltage
Minimum

18398

Float

4

R W

Volt

0 - 10

FGIMT

Analog Output
Config 1

Output
Voltage
Maximum

18400

Float

4

R W

Volt

0 - 10

FGIMT

Analog Output
Config 1

Parameter
Selection

18402

Uint32 4

R W

n/a

VA=0, VB=1, VC=2, VAB=3, VBC=4, VCA=5,
3V0=6, V1=7, V2=8, IA-1=9, IB-1=10, IC-1=11, 3I0-
1=12, I1-1=13, I2-1=14, IG-1=15, IA-2=16, IB-2=17,
IC-2=18, 3I0-2=19, I1-2=20, I2-2=21, IG-2=22,
Analog Input 1=21, Phase Frequency=23, Aux
Frequency=24, Power Factor=25, Real Power=26,
Imaginary Power=27, Apparent Power=28, Analog
Input 1-1=29, Analog Input 1-2=30, Analog Input 1-
3=31, Analog Input 1-4=32, Analog Input 2-1=33,
Analog Input 2-2=34, Analog Input 2-3=35, Analog
Input 2-4=36, RTD 1-1=37 RTD 1-2=38, RTD 1-
3=39, RTD 1-4=40, RTD 1-5=41, RTD 1-6=42, RTD
1-7=43, RTD 1-8=44, RTD 1-9=45, RTD 1-10=46,
RTD 1-11=47, RTD 1-12=48, RTD 2-1=49, RTD 2-
2=50, RTD 2-3=51, RTD 2-4=52, RTD 2-5=53, RTD
2-6=54, RTD 2-7-55, RTD 2-8=56, RTD 2-9=57,
RTD 2-10=58, RTD 2-11=59, RTD 2-12=60

FGIMT

Analog Output
Config 2

Type

18404

Uint32 4

R W

n/a

Voltage=0
Current=1

FGIMT

Analog Output
Config 2

Param
Minimum

18406

Float

4

R W

n/a

-199999.8

FGIMT

Analog Output
Config 2

Parameter
Maximum

18408

Float

4

R W

n/a

-199999.8

FGIMT

Analog Output
Config 2

Output
Current
Minimum

18410

Float

4

R W

Milliamp

4 - 20

FGIMT

Analog Output
Config 2

Output
Current
Maximum

18412

Float

4

R W

Milliamp

4 - 20

FGIMT

Analog Output
Config 2

Output
Voltage
Minimum

18414

Float

4

R W

Volt

0 - 10

FGIMT

Analog Output
Config 2

Output
Voltage
Maximum

18416

Float

4

R W

Volt

0 - 10

FGIMT