Basler Electric BE1-11 Modbus Protocol User Manual

Page 79

Advertising
background image

9424200774 Rev B

73

BE1-11

Register Table

Name

Description

Group Register

Type

Bytes Writable

Unit

Range

Style

59X-4

Time Multiplier

SG3

21236
4018*

Float

4

R W

n/a

0 - 9.9

FGIT

67

Mode

SG0

21238
4020*

Uint32

4

R W

n/a

Disabled=0
Enabled=1

FGIT

Reserved

21240-
41

67

Zero
Sequence
Mode

SG0

21242
4022*

Uint32

4

R W

n/a

VOIN=0
VOIG=1
VXIN=2
VXIG=3

FGIT

67

QVI Mode

SG0

21244
4024*

Uint32

4

R W

n/a

I=1
V=2
VI=3
Q=4
QI=5
QV=6
QVI=7

FGIT

67

Mode

SG1

21246
4026*

Uint32

4

R W

n/a

Disabled=0
Enabled=1

FGIT

Reserved

21248-
49

67

Zero
Sequence
Mode

SG1

21250
4028*

Uint32

4

R W

n/a

VOIN=0
VOIG=1
VXIN=2
VXIG=3

FGIT

67

QVI Mode

SG1

21252
4030*

Uint32

4

R W

n/a

I=1
V=2
VI=3
Q=4
QI=5
QV=6
QVI=7

FGIT

67

Mode

SG2

21254
4032*

Uint32

4

R W

n/a

Disabled=0
Enabled=1

FGIT

Reserved

21256-
57

67

Zero
Sequence
Mode

SG2

21258
4034*

Uint32

4

R W

n/a

VOIN=0
VOIG=1
VXIN=2
VXIG=3

FGIT

67

QVI Mode

SG2

21260
4036*

Uint32

4

R W

n/a

I=1
V=2
VI=3
Q=4
QI=5
QV=6
QVI=7

FGIT

67

Mode

SG3

21262
4038*

Uint32

4

R W

n/a

Disabled=0
Enabled=1

FGIT

Reserved

21264-
65

67

Zero
Sequence
Mode

SG3

21266
4040*

Uint32

4

R W

n/a

VOIN=0
VOIG=1
VXIN=2
VXIG=3

FGIT

67

QVI Mode

SG3

21268
4042*

Uint32

4

R W

n/a

I=1
V=2
VI=3
Q=4
QI=5
QV=6
QVI=7

FGIT

50-1

Mode

SG0

21270
4044*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8

FGIMT

50-1

Source

SG0

21272

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-1

Pickup

SG0

21274
4046*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-1

Time Delay

SG0

21276
4048*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-1

Direction

SG0

21278
4050*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT