Basler Electric BE1-11 Modbus Protocol User Manual

Page 115

Advertising
background image

9424200774 Rev B

109

BE1-11

Register Table

Name

Description

Group Register

Type

Bytes Writable

Unit

Range

Style

62-1

Mode

SG2

23014
5652*

Uint32

4

R W

n/a

Disabled=0
Pickup/Dropout=1
One-Shot/Non-
Retriggerable=2
One-Shot/Retriggerable=3
Oscillator=4
Integrating Timer=5
Latched=6

FGIMT

62-1

Time Delay 1

SG2

23016
5654*

Uint32

4

R W

Millisecond 0 - 9999000

FGIMT

62-1

Time Delay 2

SG2

23018
5656*

Uint32

4

R W

Millisecond 0 - 9999000

FGIMT

62-1

Mode

SG3

23020
5658*

Uint32

4

R W

n/a

Disabled=0
Pickup/Dropout=1
One-Shot/Non-
Retriggerable=2
One-Shot/Retriggerable=3
Oscillator=4
Integrating Timer=5
Latched=6

FGIMT

62-1

Time Delay 1

SG3

23022
5660*

Uint32

4

R W

Millisecond 0 - 9999000

FGIMT

62-1

Time Delay 2

SG3

23024
5662*

Uint32

4

R W

Millisecond 0 - 9999000

FGIMT

62-2

Mode

SG0

23026
5664*

Uint32

4

R W

n/a

Disabled=0
Pickup/Dropout=1
One-Shot/Non-
Retriggerable=2
One-Shot/Retriggerable=3
Oscillator=4
Integrating Timer=5
Latched=6

FGIMT

62-2

Time Delay 1

SG0

23028
5666*

Uint32

4

R W

Millisecond 0 - 9999000

FGIMT

62-2

Time Delay 2

SG0

23030
5668*

Uint32

4

R W

Millisecond 0 - 9999000

FGIMT

62-2

Mode

SG1

23032
5670*

Uint32

4

R W

n/a

Disabled=0
Pickup/Dropout=1
One-Shot/Non-
Retriggerable=2
One-Shot/Retriggerable=3
Oscillator=4
Integrating Timer=5
Latched=6

FGIMT

62-2

Time Delay 1

SG1

23034
5672*

Uint32

4

R W

Millisecond 0 - 9999000

FGIMT

62-2

Time Delay 2

SG1

23036
5674*

Uint32

4

R W

Millisecond 0 - 9999000

FGIMT

62-2

Mode

SG2

23038
5676*

Uint32

4

R W

n/a

Disabled=0
Pickup/Dropout=1
One-Shot/Non-
Retriggerable=2
One-Shot/Retriggerable=3
Oscillator=4
Integrating Timer=5
Latched=6

FGIMT

62-2

Time Delay 1

SG2

23040
5678*

Uint32

4

R W

Millisecond 0 - 9999000

FGIMT

62-2

Time Delay 2

SG2

23042
5680*

Uint32

4

R W

Millisecond 0 - 9999000

FGIMT

62-2

Mode

SG3

23044
5682*

Uint32

4

R W

n/a

Disabled=0
Pickup/Dropout=1
One-Shot/Non-
Retriggerable=2
One-Shot/Retriggerable=3
Oscillator=4
Integrating Timer=5
Latched=6

FGIMT

62-2

Time Delay 1

SG3

23046
5684*

Uint32

4

R W

Millisecond 0 - 9999000

FGIMT

62-2

Time Delay 2

SG3

23048
5686*

Uint32

4

R W

Millisecond 0 - 9999000

FGIMT

62-3

Mode

SG0

23050
5690*

Uint32

4

R W

n/a

Disabled=0
Pickup/Dropout=1
One-Shot/Non-
Retriggerable=2
One-Shot/Retriggerable=3
Oscillator=4
Integrating Timer=5
Latched=6

FGIMT

Advertising