Sbo select, Sbo operate – Basler Electric BE1-11 Modbus Protocol User Manual

Page 20

Advertising
background image

14

9424200774 Rev B

Register Table

BE1-11

SBO Select

Name

Description

Register

Type

Bytes

Writable

Range

43-1

Select

600

Uint32

4

R W

Set=1
Reset=2
Pulse=3

43-2

Select

602

Uint32

4

R W

Set=1
Reset=2
Pulse=3

43-3

Select

604

Uint32

4

R W

Set=1
Reset=2
Pulse=3

43-4

Select

606

Uint32

4

R W

Set=1
Reset=2
Pulse=3

43-5

Select

608

Uint32

4

R W

Set=1
Reset=2
Pulse=3

101

Select

610

Uint32

4

R W

Trip=1
Close=2

Local Contacts

Contact Output 1 Override State Select

612

Uint8

1

R W

Off=0
On=1

Local Contacts

Contact Output 2 Override State Select

613

Uint8

1

R W

Off=0
On=1

Local Contacts

Contact Output 3 Override State Select

614

Uint8

1

R W

Off=0
On=1

Local Contacts

Contact Output 4 Override State Select

615

Uint8

1

R W

Off=0
On=1

Local Contacts

Contact Output 5 Override State Select

616

Uint8

1

R W

Off=0
On=1

Local Contacts

Contact Output A Override State Select

617

Uint8

1

R W

Off=0
On=1

Settings Group

Select

618

Int32

4

R W

Settings Group 0=0
Settings Group 1=1
Settings Group 2=2
Settings Group 3=3

Settings Group

Direct Operate

620

Int32

4

R W

Settings Group 0=0
Settings Group 1=1
Settings Group 2=2
Settings Group 3=3

Local Contacts

Contact Output 6 Override State Select

622

Uint8

1

R W

Off=0
On=1

Local Contacts

Contact Output 7 Override State Select

623

Uint8

1

R W

Off=0
On=1

Local Contacts

Contact Output 8 Override State Select

624

Uint8

1

R W

Off=0
On=1

SBO Operate

Name

Description

Register

Type

Bytes

Writable

Range

43-1

Operate

700

Uint32

4

R W

Set=1
Reset=2
Pulse=3

43-2

Operate

702

Uint32

4

R W

Set=1
Reset=2
Pulse=3

43-3

Operate

704

Uint32

4

R W

Set=1
Reset=2
Pulse=3

43-4

Operate

706

Uint32

4

R W

Set=1
Reset=2
Pulse=3

43-5

Operate

708

Uint32

4

R W

Set=1
Reset=2
Pulse=3

101

Operate

710

Uint32

4

R W

Trip=1
Close=2

Local Contacts

Contact Output 1 Override State Operate

712

Uint8

1

R W

Off=0
On=1

Local Contacts

Contact Output 2 Override State Operate

713

Uint8

1

R W

Off=0 On=1

Local Contacts

Contact Output 3 Override State Operate

714

Uint8

1

R W

Off=0
On=1

Local Contacts

Contact Output 4 Override State Operate

715

Uint8

1

R W

Off=0
On=1

Local Contacts

Contact Output 5 Override State Operate

716

Uint8

1

R W

Off=0
On=1

Local Contacts

Contact Output A Override State Operate

717

Uint8

1

R W

Off=0
On=1