Basler Electric BE1-11 Modbus Protocol User Manual

Page 82

Advertising
background image

76

9424200774 Rev B

Register Table

BE1-11

Name

Description

Group Register

Type

Bytes Writable

Unit

Range

Style

50-3

Mode

SG1

21360
4116*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIMT

50-3

Source

SG1

21362

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-3

Pickup

SG1

21364
4118*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-3

Time Delay

SG1

21366
4120*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-3

Direction

SG1

21368
4122*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

50-3

Mode

SG2

21370
4124*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIMT

50-3

Source

SG2

21372

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-3

Pickup

SG2

21374
4126*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-3

Time Delay

SG2

21376
4128*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-3

Direction

SG2

21378
4130*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

50-3

Mode

SG3

21380
4132*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIMT

50-3

Source

SG3

21382

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-3

Pickup

SG3

21384
4134*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-3

Time Delay

SG3

21386
4136*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-3

Direction

SG3

21388
4138*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

50-4

Mode

SG0

21390
4140*

Uint32

4

R W

n/a

Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9

FGIMT

50-4

Source

SG0

21392

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50-4

Pickup

SG0

21394
4142*

Float

4

R W

Amp

0.5 - 150

FGIMT

50-4

Time Delay

SG0

21396
4144*

Float

4

R W

Millisecond 0 - 60000

FGIMT

50-4

Direction

SG0

21398
4146*

Uint32

4

R W

n/a

Forward=0
Reverse=1
Non-Directional=2

FGIT

Advertising