Register Table

Name

Description

Group Register

Type

Bytes Writable

Unit

Range

Style

Analog Input Protection 4

Pickup

SG2

23742

Float

4

R W

n/a

-999999.9 - 999999.9

FGIMT

Analog Input Protection 4

Time Delay

SG2

23744

Float

4

R W

Millisecond 0 - 60000

FGIMT

Analog Input Protection 4

Inhibit Level

SG2

23746

Float

4

R W

n/a

-99999.9 - 99999.9

FGIMT

Analog Input Protection 4

Mode

SG3

23748

Uint32

4

R W

n/a

Disabled=0
Over=1
Under=2

FGIMT

Analog Input Protection 4

Source

SG3

23750

Uint32

4

R W

n/a

Module 1 Input 1=0
Module 1 Input 2=1
Module 1 Input 3=2
Module 1 Input 4=3
Module 2 Input 1=4
Module 2 Input 2=5
Module 2 Input 3=6
Module 2 Input 4=7

FGIMT

Analog Input Protection 4

Pickup

SG3

23752

Float

4

R W

n/a

-999999.9 - 999999.9

FGIMT

Analog Input Protection 4

Time Delay

SG3

23754

Float

4

R W

Millisecond 0 - 60000

FGIMT

Analog Input Protection 4

Inhibit Level

SG3

23756

Float

4

R W

n/a

-99999.9 - 99999.9

FGIMT

Analog Input Protection 5

Mode

SG0

23758

Uint32

4

R W

n/a

Disabled=0
Over=1
Under=2

FGIMT

Analog Input Protection 5

Source

SG0

23760

Uint32

4

R W

n/a

Module 1 Input 1=0
Module 1 Input 2=1
Module 1 Input 3=2
Module 1 Input 4=3
Module 2 Input 1=4
Module 2 Input 2=5
Module 2 Input 3=6
Module 2 Input 4=7

FGIMT

Analog Input Protection 5

Pickup

SG0

23762

Float

4

R W

n/a

-999999.9 - 999999.9

FGIMT

Analog Input Protection 5

Time Delay

SG0

23764

Float

4

R W

Millisecond 0 - 60000

FGIMT

Analog Input Protection 5

Inhibit Level

SG0

23766

Float

4

R W

n/a

-99999.9 - 99999.9

FGIMT

Analog Input Protection 5

Mode

SG1

23768

Uint32

4

R W

n/a

Disabled=0
Over=1
Under=2

FGIMT

Analog Input Protection 5

Source

SG1

23770

Uint32

4

R W

n/a

Module 1 Input 1=0
Module 1 Input 2=1
Module 1 Input 3=2
Module 1 Input 4=3
Module 2 Input 1=4
Module 2 Input 2=5
Module 2 Input 3=6
Module 2 Input 4=7

FGIMT

Analog Input Protection 5

Pickup

SG1

23772

Float

4

R W

n/a

-999999.9 - 999999.9

FGIMT

Analog Input Protection 5

Time Delay

SG1

23774

Float

4

R W

Millisecond 0 - 60000

FGIMT

Analog Input Protection 5

Inhibit Level

SG1

23776

Float

4

R W

n/a

-99999.9 - 99999.9

FGIMT

Analog Input Protection 5

Mode

SG2

23778

Uint32

4

R W

n/a

Disabled=0
Over=1
Under=2

FGIMT

Analog Input Protection 5

Source

SG2

23780

Uint32

4

R W

n/a

Module 1 Input 1=0
Module 1 Input 2=1
Module 1 Input 3=2
Module 1 Input 4=3
Module 2 Input 1=4
Module 2 Input 2=5
Module 2 Input 3=6
Module 2 Input 4=7

FGIMT

Analog Input Protection 5

Pickup

SG2

23782

Float

4

R W

n/a

-999999.9 - 999999.9

FGIMT

Analog Input Protection 5

Time Delay

SG2

23784

Float

4

R W

Millisecond 0 - 60000

FGIMT

Analog Input Protection 5

Inhibit Level

SG2

23786

Float

4

R W

n/a

-99999.9 - 99999.9

FGIMT

Analog Input Protection 5

Mode

SG3

23788

Uint32

4

R W

n/a

Disabled=0
Over=1
Under=2

FGIMT

Analog Input Protection 5

Source

SG3

23790

Uint32

4

R W

n/a

Module 1 Input 1=0
Module 1 Input 2=1
Module 1 Input 3=2
Module 1 Input 4=3
Module 2 Input 1=4
Module 2 Input 2=5
Module 2 Input 3=6
Module 2 Input 4=7

FGIMT

Analog Input Protection 5

Pickup

SG3

23792

Float

4

R W

n/a

-999999.9 - 999999.9

FGIMT

Analog Input Protection 5

Time Delay

SG3

23794

Float

4

R W

Millisecond 0 - 60000

FGIMT

Analog Input Protection 5

Inhibit Level

SG3

23796

Float

4

R W

n/a

-99999.9 - 99999.9

FGIMT

Analog Input Protection 6

Mode

SG0

23798

Uint32

4

R W

n/a

Disabled=0
Over=1
Under=2

FGIMT

Advertising