Basler Electric BE1-11 Modbus Protocol User Manual

Page 57

Advertising
background image

9424200774 Rev B

51

BE1-11

Register Table

Name

Description

Register

Type

Bytes Writable

Unit

Range

Style

Analog Output
Config 4

Parameter
Selection

18450

Uint32 4

R W

n/a

VA=0, VB=1, VC=2, VAB=3, VBC=4, VCA=5,
3V0=6, V1=7, V2=8, IA-1=9, IB-1=10, IC-1=11, 3I0-
1=12, I1-1=13, I2-1=14, IG-1=15, IA-2=16, IB-2=17,
IC-2=18, 3I0-2=19, I1-2=20, I2-2=21, IG-2=22,
Analog Input 1=21, Phase Frequency=23, Aux
Frequency=24, Power Factor=25, Real Power=26,
Imaginary Power=27, Apparent Power=28, Analog
Input 1-1=29, Analog Input 1-2=30, Analog Input 1-
3=31, Analog Input 1-4=32, Analog Input 2-1=33,
Analog Input 2-2=34, Analog Input 2-3=35, Analog
Input 2-4=36, RTD 1-1=37 RTD 1-2=38, RTD 1-
3=39, RTD 1-4=40, RTD 1-5=41, RTD 1-6=42, RTD
1-7=43, RTD 1-8=44, RTD 1-9=45, RTD 1-10=46,
RTD 1-11=47, RTD 1-12=48, RTD 2-1=49, RTD 2-
2=50, RTD 2-3=51, RTD 2-4=52, RTD 2-5=53, RTD
2-6=54, RTD 2-7-55, RTD 2-8=56, RTD 2-9=57,
RTD 2-10=58, RTD 2-11=59, RTD 2-12=60

FGIMT

Motor
Configuration

Full Load
Amps

18452

Float

4

R W

Amp

1 - 25

M

Motor
Configuration

Service
Factor

18454

Float

4

R W

n/a

1 - 1.4

M

Reserved

18456-
57

M

Motor
Configuration

Motor Start
Detection

18458

Uint32 4

R W

n/a

Current Only=0
Current and Contact=1
Contact Only=2

M

Motor
Configuration

Motor Stop
Detection

18460

Uint32 4

R W

n/a

Current Only=0
Current and Contact=1
Contact Only=2

M

Reserved

18462-
63

M

Motor
Maintenance
Data

Hours
Running

18464

Uint32 4

R W

Hour

0 - 2000000

M

Motor
Maintenance
Data

Minutes
Running

18466

Uint32 4

R W

Minute

0 - 59

M

Motor
Maintenance
Data

Max Duration
Start Min

18468

Uint32 4

R W

n/a

0 - 59

M

Motor
Maintenance
Data

Max Duration
Start
Seconds

18470

Uint32 4

R W

n/a

0 - 59

M

Motor
Maintenance
Data

Total
Successful
Norm Starts

18472

Int32

4

R W

n/a

0 - 500000

M

Motor
Maintenance
Data

Total
Successful
Emergency
Starts

18474

Int32

4

R W

n/a

0 - 500000

M

Motor
Maintenance
Data

Total Fail
Norm Starts

18476

Int32

4

R W

n/a

0 - 500000

M

Motor
Maintenance
Data

Total Fail
Emergency
Starts

18478

Int32

4

R W

n/a

0 - 500000

M

Motor
Maintenance
Data

Total Number
Trips

18480

Int32

4

R W

n/a

0 - 500000

M

Motor
Maintenance
Data

Total Number
Thermal Trips

18482

Int32

4

R W

n/a

0 - 500000

M

Motor
Maintenance
Data

Maximum
Thermal Start

18484

Float

4

R W

Percent

0 - 1000

M

Motor
Maintenance
Data

Maximum Cur
Start

18486

Float

4

R W

Amp

0 - 2000000000

M

Motor
Maintenance
Data

Minimum Volt
Start

18488

Float

4

R W

Volt

0 - 2000000000

M

Motor
Maintenance
Data

Hot RTD
Group 1

18490

Float

4

R W

n/a

0 - 250

M

Motor
Maintenance
Data

Hot RTD
Group 2

18492

Float

4

R W

n/a

0 - 250

M

Motor
Maintenance
Data

Hot RTD
Group 3

18494

Float

4

R W

n/a

0 - 250

M

Advertising