Basler Electric BE1-11 Modbus Protocol User Manual

Page 121

Advertising
background image

9424200774 Rev B

115

BE1-11

Register Table

Name

Description

Group Register

Type

Bytes Writable

Unit

Range

Style

50BF

Phase Pickup

SG0

23302
5938*

Float

4

R W

Amp

0.25 - 10

FGIMT

50BF

Neutral Pickup

SG0

23304
5940*

Float

4

R W

Amp

0.25 - 10

FGIMT

50BF

Time Delay

SG0

23306
5942*

Float

4

R W

Millisecond 50 - 999

FGIMT

50BF

Control Time

SG0

23308
5944*

Float

4

R W

Millisecond 50 - 999

FGIMT

50BF

IG Source

SG0

23310

Uint32

4

R W

n/a

IG1=0
IG2=1

FGIMT

50BF

Mode

SG1

23312
5946*

Uint32

4

R W

n/a

Disabled=0
Enabled=1

FGIMT

50BF

Source

SG1

23314

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50BF

Phase Pickup

SG1

23316
5948*

Float

4

R W

Amp

0.25 - 10

FGIMT

50BF

Neutral Pickup

SG1

23318
5950*

Float

4

R W

Amp

0.25 - 10

FGIMT

50BF

Time Delay

SG1

23320
5952*

Float

4

R W

Millisecond 50 - 999

FGIMT

50BF

Control Time

SG1

23322
5954*

Float

4

R W

Millisecond 50 - 999

FGIMT

50BF

IG Source

SG1

23324

Uint32

4

R W

n/a

IG1=0
IG2=1

FGIMT

50BF

Mode

SG2

23326
5956*

Uint32

4

R W

n/a

Disabled=0
Enabled=1

FGIMT

50BF

Source

SG2

23328

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50BF

Phase Pickup

SG2

23330
5958*

Float

4

R W

Amp

0.25 - 10

FGIMT

50BF

Neutral Pickup

SG2

23332
5960*

Float

4

R W

Amp

0.25 - 10

FGIMT

50BF

Time Delay

SG2

23334
5962*

Float

4

R W

Millisecond 50 - 999

FGIMT

50BF

Control Time

SG2

23336
5964*

Float

4

R W

Millisecond 50 - 999

FGIMT

50BF

IG Source

SG2

23338

Uint32

4

R W

n/a

IG1=0
IG2=1

FGIMT

50BF

Mode

SG3

23340
5966*

Uint32

4

R W

n/a

Disabled=0
Enabled=1

FGIMT

50BF

Source

SG3

23342

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

50BF

Phase Pickup

SG3

23344
5968*

Float

4

R W

Amp

0.25 - 10

FGIMT

50BF

Neutral Pickup

SG3

23346
5970*

Float

4

R W

Amp

0.25 - 10

FGIMT

50BF

Time Delay

SG3

23348
5972*

Float

4

R W

Millisecond 50 - 999

FGIMT

50BF

Control Time

SG3

23350
5974*

Float

4

R W

Millisecond 50 - 999

FGIMT

50BF

IG Source

SG3

23352

Uint32

4

R W

n/a

IG1=0
IG2=1

FGIMT

52

Mode

GG

23354
5976*

Uint32

4

R W

n/a

Disabled=0
Enabled=1

FGIMT

Breaker Monitor

Mode

GG

23356
5978*

Uint32

4

R W

n/a

Disabled=0
Enabled=1

FGIMT

Breaker Monitor

Source

GG

23358

Uint32

4

R W

n/a

CT1=0
CT2=1

FGIMT

Breaker Monitor

Exponent

GG

23360
5980*

Float

4

R W

n/a

1 - 3

FGIMT

Breaker Monitor

Max Duty

GG

23362
5982*

Scientific 4

R W

n/a

0 - 42000000

FGIMT

Breaker Monitor

Alarm 1 Type

GG

23364
5984*

Uint32

4

R W

n/a

Disabled=0
Duty=1
Operation=2
Clearing=3

FGIMT

Breaker Monitor

Alarm 1
Threshold

GG

23366
5986*

Float

4

R W

See range

Duty: 0 – 200%
Operation: 0 – 99,999
Clearing: 0 – 1,000
milliseconds

FGIMT

Breaker Monitor

Alarm 2 Type

GG

23368
5988*

Uint32

4

R W

n/a

Disabled=0
Duty=1
Operation=2
Clearing=3

FGIMT

Breaker Monitor

Alarm 2
Threshold

GG

23370
5990*

Float

4

R W

See range

Duty: 0 – 200%
Operation: 0 – 99,999
Clearing: 0 – 1,000
milliseconds

FGIMT