9424200774 Rev B

107

BE1-11

Register Table

Name

Description

Group Register

Type

Bytes Writable

Unit

Range

Style

81-7

Over
Frequency

SG2

22912
5550*

Float

4

R W

Hertz

15 - 70

FGIT

81-7

Under
Frequency

SG2

22914
5552*

Float

4

R W

Hertz

15 - 70

FGIT

81-7

Mode

SG3

22916
5554*

Uint32

4

R W

n/a

Disabled=0
Over=1
Under=2
Rate of Change=3
Positive Rate of
Change=4
Negative Rate of
Change=5

FGIT

81-7

Pickup

SG3

22918
5556*

Float

4

R W

Hertz

15 - 70

FGIT

81-7

Time Delay

SG3

22920
5558*

Float

4

R W

Millisecond 0 - 600000

FGIT

81-7

Voltage Inhibit

SG3

22922
5560*

Float

4

R W

Volt

15 - 250

FGIT

81-7

Negative
Sequence
Inhibit

SG3

22924
5562*

Float

4

R W

Percent

0 - 99

FGIT

81-7

Over
Frequency

SG3

22926
5564*

Float

4

R W

Hertz

15 - 70

FGIT

81-7

Under
Frequency

SG3

22928
5566*

Float

4

R W

Hertz

15 - 70

FGIT

81-8

Mode

SG0

22930
5568*

Uint32

4

R W

n/a

Disabled=0
Over=1
Under=2
Rate of Change=3
Positive Rate of
Change=4
Negative Rate of
Change=5

FGIT

81-8

Pickup

SG0

22932
5570*

Float

4

R W

Hertz

15 - 70

FGIT

81-8

Time Delay

SG0

22934
5572*

Float

4

R W

Millisecond 0 - 600000

FGIT

81-8

Voltage Inhibit

SG0

22936
5574*

Float

4

R W

Volt

15 - 250

FGIT

81-8

Negative
Sequence
Inhibit

SG0

22938
5576*

Float

4

R W

Percent

0 - 99

FGIT

81-8

Over
Frequency

SG0

22940
5578*

Float

4

R W

Hertz

15 - 70

FGIT

81-8

Under
Frequency

SG0

22942
5580*

Float

4

R W

Hertz

15 - 70

FGIT

81-8

Mode

SG1

22944
5582*

Uint32

4

R W

n/a

Disabled=0
Over=1
Under=2
Rate of Change=3
Positive Rate of
Change=4
Negative Rate of
Change=5

FGIT

81-8

Pickup

SG1

22946
5584*

Float

4

R W

Hertz

15 - 70

FGIT

81-8

Time Delay

SG1

22948
5586*

Float

4

R W

Millisecond 0 - 600000

FGIT

81-8

Voltage Inhibit

SG1

22950
5588*

Float

4

R W

Volt

15 - 250

FGIT

81-8

Negative
Sequence
Inhibit

SG1

22952
5590*

Float

4

R W

Percent

0 - 99

FGIT

81-8

Over
Frequency

SG1

22954
5592*

Float

4

R W

Hertz

15 - 70

FGIT

81-8

Under
Frequency

SG1

22956
5594*

Float

4

R W

Hertz

15 - 70

FGIT

81-8

Mode

SG2

22958
5596*

Uint32

4

R W

n/a

Disabled=0
Over=1
Under=2
Rate of Change=3
Positive Rate of
Change=4
Negative Rate of
Change=5

FGIT

81-8

Pickup

SG2

22960
5598*

Float

4

R W

Hertz

15 - 70

FGIT

81-8

Time Delay

SG2

22962
5600*

Float

4

R W

Millisecond 0 - 600000

FGIT

81-8

Voltage Inhibit

SG2

22964
5602*

Float

4

R W

Volt

15 - 250

FGIT