Fronius IG 300 User Manual

Page 56

Advertising
background image

48

AC leads and a
pair of DC leads

3

L1 L2 L3 N PE PE

1

2

AC leads and a
two pairs of DC
leads

-

AC cable cross section: 35 mm²

The copper brackets on the DC side
provide enough space for up to 8 DC
cables. The fitting screws are supplied
with the FRONIUS IG.

NOTE! Do not exceed the follo-
wing torques when tightening the
screws:

-

AC terminals: 6 Nm

-

Securing the DC cables to
the copper brackets: 30 Nm
(M12 screws)

-

AC cable cross section: 35 mm²

-

DC cable cross section: 70 mm²

If two pairs of DC cables are connected to
the FRONIUS IG, they should be con-
nected directly (without using the copper
brackets).

NOTE! Do not exceed the follo-
wing torques when tightening the
screws:

-

AC terminals: 6 Nm

-

DC terminals: 7 Nm

-

After connecting the cable, replace
the cover

AC

DC

+

-

L1, L2, L3, N, PE

Strain relief

Open the strain relief device, remove it if
necessary and route the following cables
through it:
-

AC cable

-

DC cable

-

Cables for LocalNet/DatCom if they
are installed (additionally secure these
with cable ties)

-

Cables for external power supply to
the rack, if installed

1

1

2

1

3

Important! If required, request a sealing cover for the over/undervoltage relay and have
it fitted by your power supply company.

L1 L2 L3 N PE PE

2

2

1

AC

DC

+

-

L1, L2, L3, N, PE