Atlas retail, Retail data wire lengths, Commercial data wire lengths – Gasboy Atlas Fuel Systems Installation Manual User Manual
Page 67

MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014
Page 7-5
Wiring
Reference Information
Atlas Retail
The Atlas retail pump/dispenser utilizes only one main conduit as it does not require a DC
conduit. The AC conduit is used to carry the AC wire and the two-wire interface twisted-pair.
The distinction between commercial and retail pumps/dispensers units is that the commercial
unit uses a separate conduit arrangement to keep signals from interfering with one another or
other noise generating devices, whereas in the retail unit it is not critical.
When installed in a separate DC conduit, 18 AWG wires are required for the installation.
Although it is recommended that DC commercial pump interface wires (RS-485 or pulse
output) be run in a conduit away from AC wires, they can be combined in the same conduit
with AC wires, provided that a UL-listed cable with the following specifications is used:
Gasboy can supply Belden
®
1063A (part number C09655), which is a UL-listed,
four-conductor cable that meets the requirements listed above.
Note: Belden 1063A is UL-listed but not CSA-listed.
Retail Data Wire Lengths
Use the following table to determine the maximum length of the data wire:
For This Distribution Box (D-Box)
Distance Between the D-Box and
Dispenser
Distance Between the D-Box and
Console/Controller
PA0133, PA0187 G-SITE
®
“Total” data wire system run no more than 2600 feet with 14 AWG
PA0242 Transac System 1000
™
No more than 2600 feet with 14 AWG
No more than 2600 feet with 14 AWG
PA0261 Universal D-Box
No more than 2600 feet with 14 AWG
No more than 2600 feet with 14 AWG
PA0306 D-Box
No more than 2600 feet with 14 AWG
No more than 2600 feet with 14 AWG
Commercial Data Wire Lengths
Use the following table to determine maximum data wire lengths:
For This D-Box
Distance Between the D-Box and
Dispenser
Distance Between the D-Box and
Console/Controller
RS-485 Cable
No more than 1000 feet from the J-box
to the farthest CFN component
No more than 1500 feet between all
CFN components
LAN Communication
No more than 333 inches from Islander
to LAN jack
Specification
Setting
Conductor
18 AWG stranded wire. Number of conductors to be determined by pulser requirements.
Shield
Foil-wrapped 100% coverage and/or tinned copper braid 90% coverage.
Drain Wire
Stranded, tinned copper, 20 AWG or larger/or braided shield.
Voltage Rating
Maximum operating voltage of 600 V.
Environmental
Gas- and oil-resistant; suitable for wet or dry locations.