Mechanical PCU Option

Pump Control EXPMUX CPU Board

Page 86

MDE-4319E TopKAT™ Fuel Management System Installation Manual · August 2008

10

In switch bank SC, between 5 through 8, only switch 6 and 8 are active. Switch SC-6 is the
Deadman Timer Switch. If enabled, the pump control unit must be polled at least every 15
seconds by the TopKAT. If it fails to sense a poll at that time, it turns off all relays. If Reset
Complete Mode is used on any pump on a particular PCU, the deadman timer should be
disabled. Switch SC-8 enables the test mode allowing the basic PCU functions to be tested
without the use of a site controller.

The table below gives the switch settings for SC-5 through SC-8.

Switch

Function

SC-5

No function in on-line mode

SC-6

DEAD

Open = deadman timer enabled

SC-7

No function in on-line mode

SC-8

TEST

Open = Test mode, Closed = On-line mode

11

Reinstall the EXPMUX Pump Control CPU board.