Installation - Direct Gas Piping

Installation

Step 1 Determine the Supply Gas Requirements

The unit’s direct gas nameplate states the requirements for the gas being supplied to the unit.

IMPORTANT!

All gas piping must be installed in accordance with the latest edition of the National Fuel Gas Code

ANSI/Z223.1 and any local codes that may apply. In Canada, the equipment shall be installed in

accordance with the Installation Code for Gas Burning Appliances and Equipment (CGA B149) and

Provincial Regulations for the class. Authorities having jurisdiction should be consulted before

installations are made.

WARNING!

All components of this or any other gas fired heating unit must be leak tested prior to placing the unit

into operation. A soap and water solution should be used to perform this test. NEVER test for gas

leaks with an open flame.

WARNING!

If pressure testing in excess of 1/2 psig (3.5

kPa), the heater and manual shutoff valve must

be disconnected from the supply gas line.

WARNING!

If pressure testing at or below 1/2 psig (3.5 kPa),

the heater must be isolated from the supply gas

line by closing its manual shutoff valve.

IMPORTANT!

All piping should be clean and free of any foreign

matter. Foreign material entering the gas train

can damage the valves, regulators and burner.

“W.C.

“W.C.

“W.C.

F

PSI

“W.C.

“W.C.

MAX BTU/HR
BTU/H MAX

NORMAL MANIFOLD
PRESSURE
PRESSION D’ADMISSION
NORMALE

MIN GAS
PRESSURE
PRESSION DE GAZ

MIN BURNER
PRESSURE DROP
PERTE MIN DE PRESSION
DANS LE BRULEUR

TYPE OF GAS
NATURE DU GAZ

MIN BTU/HR
BTU/H MIN

MIN GAS PRESSURE
FOR MAX OUTPUT
PRESSION DE GAZ MIN
POUR PUISSANCE MAX

MAX BURNER
PRESSURE DROP
PERTE MAX DE PRESSION
DANS LE BRULEUR

MAX GAS
PRESSURE
PRESSION DE GAZ
MAX

DESIGN ∆T
∆T NORMALE

EQUIPPED FOR

CONCU POUR

SCFM

“W.C.

EXTERNAL STATIC PRESSURE

PRESSION STATIQUE EXTERIEURE

AGAINST

CONTE

Maximum gas

pressure

Minimum gas

pressure for

maximum output

Type of Gas

IMPORTANT!

Do NOT connect the unit to gas types other than

what is specified and do NOT connect the unit

to gas pressures that are outside of the pressure

range shown on the label.

Direct Gas Nameplate