36

Troubleshooting

Troubleshooting

No

Check for proper pilot pressure.

(Direct Gas Start-Up #2)

Check inlet gas pressure.

(Direct Gas Start Up Step #1)

Note: The minimum and maximum gas pressures for your unit are

shown on the direct gas label. Reference start-up procedure #1

Gas pressure between the min

and max shown on the direct gas

label?

Correct gas pressure

(Reference Direct Gas Start-Up Step #1)

Proper spark?

Crossed flame and spark wires

(Uncross wires and reconnect)

Incorrect spark plug gap

(Set spark plug gap to 0.062 in.)

Defective spark plug

(Replace spark plug)

Pressure drop across the

burner between 0.625 and

0.675 in. wc?

Adjust burner baffles

(Reference Direct Gas Start-Up Step #4)

Check for proper airflow

(Direct Gas Start-Up Step #4)

Note: The airflow may satisfy the airflow switch, but may make

lighting the pilot difficult. Adjust the pressure drop across the burner

to 0.625 in. wc shown in Direct Gas Start-Up Step #4.

Air in the gas line?

Purge gas line

(Verify gas at the pilot)

No

No

Yes

No

No

Yes

Yes

Yes

Yes

No

Note: A high pilot pressure will make lighting more difficult. Lower the

pilot pressure in increments until the unit lights. Then set the pilot per

the instruction in Direct Gas Start-Up procedure #2)

Yes

Adjust the pilot pressure

(Reference Direct Gas Start-Up Step #2)

Heater Does Not Operate

Attempts to light but no visible pilot (Visible spark)

Pilot pressure correct?

Yes

With proper airflow, gas pressure and spark,

the unit should light.

If problems remain, consult the factory

Advertising