Start-Up - Direct Gas

Step 7 Set the Minimum Firing Rate

Disconnect and isolate one of the wires running to the
modulating valve to send the unit to its minimum
firing rate. Set the minimum firing rate by adjusting
the needle valve as shown in the figures below.

After setting the minimum firing rate, shut off the pilot
to ensure that the flame safeguard can still read the
main flame signal. Reconnect the wire to the
modulating valve and open the pilot shut-off valve.

Remove one wire to

send the unit to the

minimum firing rate.

Minimum

firing rate

adjustment

Remove one wire to

send the unit to the

minimum firing rate.

NOTE!

Gas trains are equipped with either separate regulators and modulating valves or with a combined

modulating regulator.

NOTE!

On units with a 42 inch or greater burner, the flame safe guard will automatically shut off the pilot

after the burner has been ignited.

IMPORTANT!

The proper setting for the minimum firing rate

results in a small ribbon of continuous flame

across the entire burner.

IMPORTANT!

Do not allow the disconnected wire to come in

contact with a potential ground, damage to the

amplifier or transformer could result.

NOTE!

Adjusting the maximum and minimum firing rate requires the inlet air sensor to be set higher than the

outdoor air temperature in order to start the burner(s). Once high and low fire have been set, the inlet

air sensor should be set to the desired temperature.

NOTE!

Counterclockwise rotation increases the

minimum fire rate setting, clockwise rotation

decreases the setting.

Separate Regulator and
Modulating Valve

Combined Modulating
Regulator

Minimum firing rate

adjustment