Troubleshooting, Heater does not operate – Greenheck DG / DGX with Pilot Ignition (463555 IOM) (Pre-2008) User Manual

Page 35

Advertising
background image

35

Troubleshooting

24 Vac between

terminals W1 and X?

Heat Switch (S4) Off

(Turn Heat Switch S4 On)
Heat Switch Not Wired

(Wire Heat Switch S4)

115 Vac between

terminals 102 and 101?

Primary Fuses Blown

(Replace Fuses)

Main Transformer Defective

(Replace Transformer)

115 Vac between

terminals 106 and 101?

High/Low Gas Pressure Switch Tripped

(Correct gas pressure and reset)

(Reference Direct Gas Start-Up Step #2 and #3)

115 Vac between

terminals 104 and 101?

High Limit (HLC) Tripped

(Reset/Replace High Limit HLC)

(Check on cause of control loss)

Continuity between

terminals 107 and 108?

Note: The power light on the flame safeguard should blink

approximately every 5 seconds as it performs

a self-diagnostics check.

115 Vac between

terminals 103 and 101?

Inlet Air Sensor (TS) Holding

(Adjust TS setting -- Reference Blower Start-Up step 6)

Heat Relay (RH) Defective

(Replace Heat Relay RH)

No

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Airflow Switch (PS) Holding for Proper Air Flow

(Correct airflow across burner)

(Reference Direct Gas Start-Up Step #4)

Yes

At this time the heater should attempt to light

(The pilot light on the flame safeguard should illuminate)

Heater Does Not Operate

Does not attempt to light (No visible spark)