22

Start-Up

7

6

0.625 - 0.675 in. wc

Start-Up - Direct Gas

Step 4 Set the Burner Air Pressure

Differential

With the fan running and discharging 70°F air,
connect a U-Tube manometer to the outer sensing
probes (see below) and measure the static pressure
across the burner.

The proper static pressure should be between 0.625
and 0.675 inches w.c. Evenly adjust the baffles above
and below the burner, keeping the burner centered in
the opening until the required pressure is obtained.

Outer Sensing Probes

Adjustable
Top Baffle

Airflow

Burner

Adjustable
Bottom Baffle

IMPORTANT!

Proper air velocity over the burner is critical on direct fired gas units. If the air velocity is not within

the unit specifications, the unit will not operate efficiently, may have sporadic shutdowns and may

produce excessive carbon monoxide (CO) or other gases.

NOTE!

To increase the static pressure decrease the

opening. To decrease the static pressure

increase the opening.

IMPORTANT!

This process may need to be repeated until the

proper pressure is achieved. This adjustment

will change the air quantity delivered by the unit

and therefore the air quantity delivered should be

rechecked. Refer to the blower start-up section.

NOTE!

When required pressure is obtained, be sure to

reconnect the outer sensing probes.

Measuring the Burner Pressure Drop

Burner and Baffles