Start-up - direct gas, Maxitrol series 44, Maxitrol series 14 – Greenheck DG / DGX with Pilot Ignition (463555 IOM) (Pre-2008) User Manual

Page 23: Step 6 set the maximum firing rates, Step 5 set the low fire time delay, Warning

Advertising
background image

23

Remove the wire from terminal #4 to

send the unit to maximum fire

Start-Up - Direct Gas

Low fire time delay setting

(75% of maximum)

Remove the wire from the #3 terminal to send

the unit to maximum fire

Maximum discharge temperature

setting (100°F Typical)

Minimum discharge
temperature setting

(50°F Typical)

Low fire time delay

setting

(75% of maximum)

Step 6 Set the Maximum Firing Rates

Monitor the units actual temperature rise by placing a
thermocouple in the unit’s inlet and a second in the
discharge, three duct diameters downstream of the
burner.

Send the unit to maximum fire by disconnecting and
isolating the proper wire on the Maxitrol amplifier.
(Terminal #4 for Maxitrol 14, #3 for Maxitrol 44 as
shown below).

Continues on next page...

Step 5 Set the Low Fire Time Delay

Set the low fire time delay to 75% of its maximum
setting. See the drawings below for the location of
the time delay setting.

WARNING!

Do not set the burner maximum firing rate based

on gas pressure. It should be set based on the

unit’s designed temperature rise shown on the

direct gas label.

“W.C.

F

PSI

MAX BTU/HR
BTU/H MAX

NORMAL MANIFOLD
PRESSURE
PRESSION D’ADMISSION
NORMALE

MIN GAS
PRESSURE
PRESSION DE GAZ

MIN BURNER
PRESSURE DROP
PERTE MIN DE PRESSION
DANS LE BRULEUR

TYPE OF GAS
NATURE DU GAZ

MIN BTU/HR
BTU/H MIN

MIN GAS PRESSURE
FOR MAX OUTPUT
PRESSION DE GAZ MIN
POUR PUISSANCE MAX

MAX BURNER
PRESSURE DROP
PERTE MAX DE PRESSION
DANS LE BRULEUR

MAX GAS
PRESSURE
PRESSION DE GAZ
MAX

DESIGN ∆T
∆T NORMALE

EQUIPPED FOR

CONCU POUR

SCFM

“W.C.

EXTERNAL STATIC PRESSURE

PRESSION STATIQUE EXTERIEURE

AGAINST

CONTE

Start-Up

Direct Gas Nameplate

Maxitrol Series 44

(9 terminals)

Maxitrol Series 14

(7 terminals)

Advertising