Step 6 Seal Weatherhood Seam

Using an appropriate sealant, seal the seam between
the weatherhood and the unit.

4

Step 3 Apply Sealant

Apply an appropriate sealant around the perimeter of
the curb and duct adapter(s) to isolate fan vibration
and prevent water penetration.

Step 1 Install Curb and/or Equipment

Support(s)

Position curb/equipment support(s) on the roof
(reference the CAPS submittal for placement of
curb/equipment support(s) in relation to the unit).
Verify that unit supports are level, shim if necessary.
Attach curb to roof and flash into place. Attach the
equipment support(s) to the roof, remove metal cover,
flash to wooden nailer and reinstall cover.

Step 2 Install Ductwork

Good duct practices should be followed for all
ductwork. All ductwork should be installed in
accordance with SMACNA and AMCA guidelines,
NFPA 96 and all local codes. Reference the CAPS
submittal for ductwork sizes.

Step 4 Install Unit

Use a crane and a set of spreader bars hooked to the
factory lifting lugs to lift and center the unit on the
curb/equipment support(s).

Use self-tapping sheet metal screws to fasten the unit
to the curb/equipment support(s).

Step 5 Assemble and Attach

Weatherhood

The weatherhood can now be assembled and
attached to the unit. Detailed assembly instructions
can be found with the weatherhood. If the optional
evaporative cooling module was selected, this step
does not apply, refer to the installation instructions for
the optional evaporative cooling module.

Supply Air Duct Work
(Arrangement DB only)

Optional Return Air Duct
(Arrangement HZ and DB)

Sealant

Installation - Arrangement DB / HZ

Installation

NOTE!

The use of all lifting lugs and a set of spreader

bars is mandatory when lifting the unit.

NOTE!

Some units come with the weatherhood attached

and step 5 may not apply.

NOTE!

The use of a duct adapter is recommended on a

downblast (DB) arrangement to align the

ductwork with the supply unit. The duct adapter

is only a guide and is not to be used as support

for the ductwork.

Metal Cover

Equipment
Support

Roof Curb

Roof Curb

Ductwork

Setting Unit

Complete Rooftop Installation